Omron Sysmac NX Series User Manual page 126

Machine automation controller analog i/o units high-speed analog input units
Hide thumbs Also See for Sysmac NX Series:
Table of Contents

Advertisement

7 I/O Data and List of Settings
Data name Data type Default value I/O port name Unit Index number (hex)
Ch3 Status
WORD
Ch4 Status
WORD
The bit configuration and the description of each bit for the Ch£ Status are given in the following ta-
ble.
Bit
Data name
0
Ch£ Disconnection
Detection Status
1
Ch£ Under Range
2
Ch£ Over Range
3
Ch£ Digital Low-
pass Filter Disabled
4
Ch£ Moving Average
Filter 1 Disabled
5
Ch£ Moving Average
Filter 2 Disabled
6
Ch£ Zero Set Exe-
cuting
7
Ch£ Trigger Input
8 to
Ch£ Reserved
15
*1.
1 is TRUE and 0 is FALSE.
Ch£ Trigger Input Time Stamp
This indicates the DC time at which the trigger input changes from OFF to ON during the NX bus I/O
refresh cycle. If the trigger input changes from OFF to ON more than once during the cycle, the DC
time at the first change is recorded. Refer to 8-10 Trigger Input on page 8 - 40 for details on the appli-
cations of this data and the timing when it is obtained.
Data name
Ch1 Trigger Input Time
Stamp
Ch2 Trigger Input Time
Stamp
Ch3 Trigger Input Time
Stamp
Ch4 Trigger Input Time
Stamp
The bit configuration of the Ch£ Trigger Input Time Stamp (ULINT) is given in the following table.
7 - 8
0000 hex
Ch3 Status
0000 hex
Ch4 Status
Description
1: A disconnection was detected.
0: A disconnection was not detected.
1: An under range was detected.
0: An under range was not detected.
1: An over range was detected.
0: An over range was not detected.
1: The digital low-pass filter is disabled.
0: The digital low-pass filter is enabled.
1: The moving average filter 1 is disabled. Or
it has not reached the average count.
0: The moving average filter 1 is enabled.
1: The moving average filter 2 is disabled. Or
it has not reached the average count.
0: The moving average filter 2 is enabled.
1: The zero set is in progress.
0: The zero set is not in progress.
1: The trigger input is ON.
0: The trigger input is OFF.
---
Default
Data type
value
ULINT
0
Ch1 Trigger Input Time
Stamp
ULINT
0
Ch2 Trigger Input Time
Stamp
ULINT
0
Ch3 Trigger Input Time
Stamp
ULINT
0
Ch4 Trigger Input Time
Stamp
NX-series Analog I/O Units User's Manual for High-speed Analog Input Units (W592)
---
6003
---
6004
Data
*1
type
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
---
I/O port name
Unit
ns
ns
ns
ns
Subindex number
(hex)
01
01
I/O port name
Ch£ Disconnection
Detection Status
Ch£ Under Range
Ch£ Over Range
Ch£ Digital Low-
pass Filter Disabled
Ch£ Moving Aver-
age Filter 1 Disabled
Ch£ Moving Aver-
age Filter 2 Disabled
Ch£ Zero Set Exe-
cuting
Ch£ Trigger Input
---
Index
Subindex
number
number
(hex)
(hex)
6001
02
6002
02
6003
02
6004
02

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sysmac nx-had401Sysmac nx-had seriesSysmac nx-had402