-5.1 V -5 V
Fixed at the
lower limit in
case of -5.1 V
or less.
Input Range: 0 to 10 V
A voltage of 0 to 10 V is converted to a signed integer value (0 to 32000).
The resolution is 1/32000.
The input voltage range for which conversion is possible is -0.2 to 10.2 V and the converted value is a
signed integer value (-640 to 32640).
The disconnection detection function is not supported.
Converted value
(decimal)
+32640
+32000
Fixed at the
lower limit in
case of -0.2 V
or less.
0
-640
-0.2 V
Input Range: 0 to 5 V
A voltage of 0 to 5 V is converted to a signed integer value (0 to 32000).
The resolution is 1/32000.
The input voltage range for which conversion is possible is -0.1 to 5.1 V and the converted value is a
signed integer value (-640 to 32640).
The disconnection detection function is not supported.
NX-series Analog I/O Units User's Manual for High-speed Analog Input Units (W592)
Converted value
(decimal)
+32640
+32000
0
0 V
-32000
-32640
0 V
6 Input Range and Converted Values
Voltage
+5 V+5.1 V
Fixed at the upper
limit in case of
+5.1 V or more.
Fixed at the upper
limit in case of
+10.2 V or more.
Voltage
+10 V +10.2 V