3.6 Recommended mounting position

CAUTION!
Follow these recommendations to make sure that the device measures correctly. They have an
effect on the performance of the device.
We recommend that you prepare the installation when the tank is empty.

3.6.1 General notes

Recommended nozzle position for solids
Figure 3-4: Recommended nozzle position for solids
1 Position of the process fitting from the silo wall, r/2 (for the DN40 or DN70 Lens antenna)
2 Radius of the silo, r
3 The minimum measured level for a device without a 2° slanted PP flange option or orientation system (max. 30°)
4 The minimum measured level for a device with a 2° slanted PP flange option or orientation system (max. 30°)
INFORMATION!
If there is a nozzle on the tank before installation, the nozzle must be a minimum of 200 mm /
7.9
¨
from the tank wall. The tank wall must be flat and there must not be obstacles adjacent to
the nozzle or on the tank wall.