OPERATION
6
Menu
Function
No.
C4 Output
C4.1 Current Output 1
C4.1 Current Output 1
C4.1 Current Output 1
C4.1 Current Output 1
C4.1.1
Current Out. 1
Var.
C4.1.2
0% Range
C4.1.3
100% Range
C4.1.4
Current Out.
Range
C4.1.5
Error Function
82
Function description
Make a selection from the available output
functions to scale the current output values.
This is not shown in the Normal mode.
Minimum access level to change the
Minimum access level to change the
Minimum access level to change the
Minimum access level to change the
setting: Expert
setting:
setting:
setting:
Give a measurement value to 0% output
(refer also to menu item C4.1.1 Current Out.
C4.1.1 Current Out.
C4.1.1 Current Out.
C4.1.1 Current Out.
1 Var
1 Var for the output function). 0% output =
1 Var
1 Var
4 mA. It is possible to have an output less
than 4 mA (<0%) if you set C4.1.4 Current
Out. Range to "3.8-20.5 mA".
Minimum access level to change the
Minimum access level to change the
Minimum access level to change the
Minimum access level to change the
setting:
setting: Expert
setting:
setting:
Give a measurement value to 100% output
(refer also to menu item C4.1.1 Current Out.
C4.1.1 Current Out.
C4.1.1 Current Out.
C4.1.1 Current Out.
1 Var
1 Var
1 Var
1 Var for the output function). 100% output =
20 mA. It is possible to have an output more
than 20 mA (>100%) if you set C4.1.4 Current
Out. Range to "3.8-20.5 mA".
Minimum access level to change the
Minimum access level to change the
Minimum access level to change the
Minimum access level to change the
setting: Expert
setting:
setting:
setting:
This menu item sets the limits of the output
current range to 1 of 4 available options:
standard limits (4...20 mA), NAMUR NE 43-
compliant limits (3.8...20.5 mA), reversed
standard limits and reversed NAMUR NE
43-compliant limits. You use standard limits
when you want the 0% output to be 4 mA and
the 100% output to be 20 mA. You use
reversed limits when you want the 0%
output to be to be 20 mA and 100% output to
be 4 mA.
Minimum access level to change the
Minimum access level to change the
Minimum access level to change the
Minimum access level to change the
setting:
setting: Expert
setting:
setting:
This sets the behaviour of current output 1 if
an error occurs. If this menu item is set to
"Off", no signal is given (this parameter is
not available if menu item C4.1.4 is set to
"3.8-20.5 mA" (NAMUR) or "3.8-20.5 mA
(reversed)"). If this menu item is set to
"Hold", the output current stays at the value
where the error occurred (this parameter is
not available if menu item C4.1.4 is set to
"3.8-20.5 mA" (NAMUR) or "3.8-20.5 mA
(reversed)"). If this menu item is set to
"Low", the output current changes to 3.5 mA
(default value) if an error occurs. If this
menu item is set to "High", the output
current changes to 21.5 mA (default value) if
an error occurs. You can change the low
error current value in menu item C4.1.7. You
can change the high error current value in
menu item C4.1.8.
Minimum access level to change the
Minimum access level to change the
Minimum access level to change the
Minimum access level to change the
setting: Expert
setting:
setting:
setting:
www.drexelbrook.com
Selection list
Level, Distance, Sensor
Value, Reflection
2
min-max:
+06
+06
-4.9
...+5.1
mm /
+03
+03
-192.91
...+200.79
/
-16076...+16732 ft
min-max:
+06
+06
-4.9
...+5.1
mm /
+03
+03
-192.91
...+200.79
/
-16076...+16732 ft
4-20 mA, 3.8-20.5 mA
(NAMUR), 4-20 mA
(reversed), 3.8-20.5 mA
(reversed)
Off, Low, High, Hold
DR6500-PM-English-Issue 1
DR6500
Default
Level
1
0.0 mm
1
C1.2 Tank
Height - C1.5
Blocking
Distance
1
4-20 mA
1
Hold
1