OPERATION
6
Status
Error message
type
F F F F
Configuration
Configuration
Configuration
Configuration
Inconsistent NVRAM
Incons. Converter Calib.
Incons. Sensor Calibration
NVRAMs Mismatch
Conv. NVRAM Layout Error
Disp. NVRAM Layout Error
CO Float Error
C C C C
Electronics
Electronics
Electronics
Electronics
FW Update
108
Description
Incorrect data in the parameter
memory.
Incorrect calibration data in the
converter module.
Incorrect calibration data in the
sensor module.
The serial number of the display
screen does not agree with the
serial number of the electronics
module.
Incorrect data in the parameter
memory.
Incorrect data after an update of
the firmware.
The device cannot use the
2
measurement data because the
device settings are incorrect.
A firmware update of the
converter module continues.
www.drexelbrook.com
Corrective action
De-energize and then energize the
device again.
If the message is shown again, tell
the supplier.
Tell the supplier.
Make sure that the display screen
agrees with the electronic module.
Go to Full Setup
Full Setup > Device
Device >
Full Setup
Full Setup
Device
Device
Information
Information and record the data in
Information
Information
menu items C7.1.5 Electronic
C7.1.5 Electronic
C7.1.5 Electronic
C7.1.5 Electronic
Revision
Revision and C7.1.6 Software
C7.1.6 Software
Revision
Revision
C7.1.6 Software
C7.1.6 Software
Revision
Revision
Revision. If it is necessary, tell the
Revision
supplier.
De-energize and then energize the
device again.
If the message is shown again, tell
the supplier.
You must make the device go back
to its factory settings. Enter
Program mode. Set the device to
the "Expert" access level. Go to
Full Setup > Device
Full Setup
Device > Factory
Factory
Full Setup
Full Setup
Device
Device
Factory
Factory
Default
Default > Reset to Factory
Reset to Factory
Default
Default
Reset to Factory
Reset to Factory
Default?
Default?
Default?
Default? and set this menu item to
"Yes". Then go back to Normal
mode and set the "Save
Configuration?" page to "Yes". De-
energize and then energize the
device again.
If the message is shown again, tell
the supplier.
Wait for the firmware update to
finish.