Ametek DR6500 Handbook page 94

80 ghz radar (fmcw) level transmitter for powders and dusty atmosphere
Table of Contents

Advertisement

OPERATION
6
Procedure
Screen
94
Steps
2 × [> > > > ], 2 × [ ] and [> > > > ].
If it is the default password: 2 × [> > > > ],
5 × [ ], [> > > > ] and 8 × [ ]
[^ ^ ^ ^ ] to confirm.
[ ], [> > > > ], [ ] and 2 × [> > > > ].
[ ] or [ ] for the selection of the
empty spectrum type (Full
(Average), Full (Max), Partial
(Average), Partial (Max)).
[^ ^ ^ ^ ] to confirm.
[> > > > ] to change the position of the
cursor.
[ ] to decrease the value (or move
the decimal point one digit to the
left) or [ ] to increase the value (or
move the decimal point one digit to
the right).
[^ ^ ^ ^ ] to confirm.
[^ ^ ^ ^ ] to confirm.
[ ] or [ ] to change the parameter
("No" or "Yes").
[^ ^ ^ ^ ] to confirm.
www.drexelbrook.com
Description
Default screen.
Enter Program mode and go to menu item
A3 Login.
Enter the password used at this time for
the "Expert" access level. If it is the default
password, enter "0058".
Push these buttons to start the Record
Spectrum (Empty Spectrum) procedure.
Empty spectrum type. Make a selection
from the list of parameters. If you can
empty the tank, set this menu item to "Full,
Average" or "Full, Max". If you cannot
empty the tank, set this menu item to
"Partial, Average" or "Partial, Max".
If you use air blowers to decrease the angle
of the product surface, set Empty Spectrum
Type to "Partial, Max".
Type
Type
Type
Partial distance. If you set Empty Spectrum
Type to "Partial, Average" or "Partial, Max",
Type
Type
Type
you will have one more step to do in this
procedure. You must give a "partial
distance" value less than or equal to the
distance to the product surface from the
flange facing or thread stop of the process
connection.
CAUTION!
CAUTION!
CAUTION!
CAUTION!
If the "partial distance" value is more than
the distance to the product surface, then
the device will filter the level signal and the
device will not measure the level of the
product correctly.
Make sure that the tank is empty or it
contains not more than the minimum
quantity. Energize and operate all
equipment that moves in the silo.
Start recording? Set this menu item to
"Yes" to continue to the subsequent step.
Set this menu item to "No" to go back to the
menu.
DR6500-PM-English-Issue 1
DR6500
Empty Spectrum
Empty Spectrum
Empty Spectrum
Empty Spectrum
Empty Spectrum
Empty Spectrum