Further Information On Device Configuration In Program Mode; Standard Setup - Ametek DR6500 Handbook

80 ghz radar (fmcw) level transmitter for powders and dusty atmosphere
Table of Contents

Advertisement

OPERATION
6
Menu
Function
No.
C7.5.5
Mass
C7.5.6 Cst. Mass
C7.5.6.1
Text
C7.5.6.2
Offset
C7.5.6.3
Factor
C7.6 Factory Default
C7.6 Factory Default
C7.6 Factory Default
C7.6 Factory Default
C7.6.1
Reset to Fact.
Def.?
1 If no value or parameter is specified in the customer order
2 "Lin. Distance" and "Lin. Level" are available if you created a linearized value table in menu C3 Conversion. "Volume" and "Ullage Vol-
ume" are available if you created a level-volume table in menu C3 Conversion. "Mass" and "Ullage Mass" are available if you created
a level-mass table in menu C3 Conversion.

6.4 Further information on device configuration in Program mode

6.4.1 Standard setup

Use this procedure (menu item A4.1 Standard Setup) to change the length unit, tank type, tank
height, current output variable, 0% range, 100% range, current output range and error function.
Values and parameters that can be changed are shown between the « ... » marks in the
illustrations that follow. Push the keypad buttons in the correct sequence:
CAUTION!
Make sure that you do this procedure before you use the device. The settings in this procedure
have an effect on the performance of the device.
INFORMATION!
Current output and LCD display settings
Current output and LCD display settings
Current output and LCD display settings
Current output and LCD display settings
When you do the Standard setup
page of the LCD display (in Normal mode) automatically uses settings with the same parameters
and values as the current output settings (measurement variable, 0% range and 100% range).
The first measurement page shows "one value and bar" by default. If you must show one or more
measurement values that are different to the transmitted output signal, change the settings in
the C6.4 1st Meas. Page and C6.5 2nd Meas. Page menus. For more data, refer to Function
description on page 71
90
Function description
The mass unit shown in Normal mode if you
made a mass table in the C3 Conversion
menu. If you set this menu item to "Cst.
Mass" (custom mass unit), enter values in
menu items C7.5.6.1 thru C7.5.6.3.
Minimum access level to change the
Minimum access level to change the
Minimum access level to change the
Minimum access level to change the
setting: User
setting:
setting:
setting:
Enter a text (8 characters maximum) for the
custom volume unit.
Enter an offset value.
Enter a factor. Multiply the measured value
by this factor to change kg (kilogram) to the
custom mass unit.
If you set this menu item to "YES", the
device goes back to its initial settings (set by
the manufacturer in the factory).
Minimum access level to change the
Minimum access level to change the
Minimum access level to change the
Minimum access level to change the
setting:
setting: Expert
setting:
setting:
Standard setup procedure, the measurement value on the first measurement
Standard setup
Standard setup
table C. Full Setup menu (C6 Display).
www.drexelbrook.com
Selection list
kg, t, lb, tn.sh., tn.l., Cst.
Mass
Yes, No
DR6500-PM-English-Issue 1
DR6500
Default
kg
Cst.
0.0kg
1.0
No