Ametek DR6500 Handbook page 121

80 ghz radar (fmcw) level transmitter for powders and dusty atmosphere
Table of Contents

Advertisement

DR6500
Input and output
Current output
Current output
Current output
Current output
Output signal
Output type
Resolution
Temperature drift
Error signal
HART®
HART
HART
HART
Description
Version
Load
Digital temperature drift
Multi-drop operation
Available drivers
PROFIBUS PA (pending)
PROFIBUS PA
PROFIBUS PA
PROFIBUS PA
Type
Function blocks
Device power supply
Polarity sensitivity
Basic current
DR6500-PM-English-Issue 1
Standard: 4...20 mA
Options: 3.8...20.5 mA acc. to NAMUR NE 43; 4...20 mA (reversed); 3.8...20.5 mA
(reversed) acc. to NAMUR NE 43
Passive
±5 µA
Typically 50 ppm/K
High: 21.5 mA; Low: 3.5 mA acc. to NAMUR NE 43
Digital signal transmitted with the current output signal (HART® protocol)
7.4
≥ 250 Ω
Max. ±15 mm / 0.6¨ for the full temperature range
Yes. Current output = 4 mA. Enter Program mode to change the polling address
(1...63).
FC475, AMS, PDM, FDT/DTM
PROFIBUS MBP interface that agrees with IEC 61158-2 with 31.25 kbit/s; voltage
mode (MBP = Manchester-Coded, Bus-Powered)
1 × Transducer Block Level (TB-Level), 1 × Physical Block (PB), 4 × Analog Input
Block (AI), 1 × Totalizer Function Block (TOT)
9...32 V DC – bus powered; no additional power supply required
No
18 mA
www.drexelbrook.com