INFORMATION!
Current output and LCD display settings
Current output and LCD display settings
Current output and LCD display settings
Current output and LCD display settings
When you do the Standard setup
page of the LCD display (in Normal mode) automatically uses settings with the same parameters
and values as the current output settings (measurement variable, 0% range and 100% range).
The first measurement page shows "one value and bar" by default. If you must show one or more
measurement values that are different to the transmitted output signal, change the settings in
the C6.4 1st Meas. Page and C6.5 2nd Meas. Page menus. For more data, refer to Function
description on page 71
Measurement data includes different measurement types (level, distance, volume, ullage
volume, mass etc.). Some measurement types will only be available in Normal mode if you
entered the correct parameters in Program mode. Normal mode shows abbreviations of
measurement types if the measurement page is configured to show more than one
measurement value. For a list of the abbreviations used in Normal mode, refer to the table that
follows:
Abbreviations of measurement types used in Normal mode
Measurement type
Distance
Level
Reflection
Sensor value
Volume
Ullage volume
Mass
Ullage mass
Linearized distance
Linearized level
DR6500-PM-English-Issue 1
Standard setup procedure, the measurement value on the first measurement
Standard setup
Standard setup
table C. Full Setup menu (C6 Display).
Abbreviation
Dis
Lvl
Ref
SV
Vol
Ull
M
UllM
Ldis or Distance Lin.
LLvl or Level Lin.
www.drexelbrook.com