3.4.6
"Scenes" parameter
window
© 2006 ABB STOTZ-KONTAKT GmbH
Functional description
Fig. 13:

"Scenes" parameter window

In the Scenes parameter window, the general settings for the lightscenes
(maximum 15) are undertaken. Any two scenes for dynamic operation can
be used. Both of these scenes are assigned to dynamic mode in the
"Dynamic" parameter window.
The DALI samples included to the scene have to be individual parameterises
with the brightness value (light scene value). Through this the DALI sample
will activated for a scene. Every single DALI sample of the main channel A
and auxiliary channel B can be included in the same scene.
The devices which are not to be included in the scene should be omitted
using the "no change" setting in the "Device Lightscene value" parameter.
Each of the 15 lightscenes can be accessed and stored using the 1-bit
and/or 1-byte telegram. Both communication objects are always visible and
can be used independently of one another.
The telegram value has the following function with 1-bit control:
Telegram value "0" = retrieve scene 1
Telegram value "1" = retrieve scene 2
The following applies with the 1-byte telegram value:
EIB / KNX 1-byte telegram value
00 or 64
01 or 65
02 or 66
...
14 or 78
128 or 192
129 or 193
130 or 184
...
191 or 206
Table 6
Retrieve / store scenes
Meaning
Retrieve scene 1
Retrieve scene 2
Retrieve scene 3
...
Retrieve scene 15
Store scene 1
Store scene 2
Store scene 3
...
Store scene 15