ABB DG/S 1.1 Product Manual page 58

I-bus eib / knx dali-gateway
Table of Contents

Advertisement

®
ABB i-bus
EIB / KNX
© 2006 ABB STOTZ-KONTAKT GmbH
Functional description
No.
Function
16
Selected Device Device
&
34
Failure
Channel X Selected Device Device Failure [EIS 1; 1-bit switching]: A fault message of
the DALI device selected beforehand with the "Select Device" object (no. 7) can be
transmitted or read via this object (e.g. for maintenance purposes), depending on the
parameter setting (Status parameter window).
Telegram value
"1": Fault of one or more ballasts on the channel
"0": No fault
In order to guarantee correct operation, the gateway has to know how many
ballasts are to be monitored. This is implemented by activating the object
"Detect ballasts" (no. 251) just once. Using this function, the DALI-Gateway
independently determines how many ballasts are connected and uses this
number as a reference value. If this system has to be extended or reduced, the
"Detect ballasts" option should be reactivated. This procedure is necessary if
the number of ballasts per channel has changed, and not with the exchange of
a ballast on the same channel. The same function as for the object "Detect
ballasts" can be manually triggered if the test button on the DALI device is
pressed for longer than 5 seconds.
17
Free unused
&
35
Table 8
Communication objects for "Channel X"
For auxiliary channel B (DALI output), the corresponding communication
objects 25 to 35 apply.
Object name
Data type
Channel A or
1 bit (EIS 1)
Channel B
DPT 1.005
Channel A or
Channel B
Flags
C, R, T
54

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents