© 2006 ABB STOTZ-KONTAKT GmbH
Project design and programming
Note: With this parameterisation, telegrams on object channel A "On/Off"
automatically control both dynamic scenes. Thus no normal central switching
on/off procedure in channel A is possible.
Fig. 28
Staircase lighting – Dynamic parameterisation
The start and end scene are selected in the "Dynamic" window. In our case it
is scene 8 and 9. The hold times of the scenes will be parameterised.
Fig. 29
Staircase lighting – Select start and end scene
After the scenes have been selected, the scene parameters hold value and
transition value must be set. This is implemented in the "Scenes" parameter
window where the devices are also assigned. It is important to ensure that
the devices which are not used in the staircase are set to "no change"
(Device xy Lightscene value) – the default setting.
Fig. 30
Staircase lighting – Start scene parameterisation
73