Parameter window:
Scenes
44
Project design and programming
The general settings for the lightscenes (maximum 16) are carried out in the
Scenes parameter window.
Fig. 24: Scenes parameter window - General scene parameters
Activate lightscenes: The lightscenes (max. 16) are activated with this
parameter. The number of visible communication objects and parameter
windows changes accordingly.
Control scenes via: Lightscenes can be retrieved and saved via 1-bit
and/or 1-byte telegrams. The number and type of the visible communication
objects changes according to the selected setting.
With 1-bit control, the telegram value has the following function:
Telegram value "0" = Recall scene 1
Telegram value "1" = Recall scene 2
With the 1-byte telegram value, the following applies:
KNX 1 byte telegram value
dezimal
hexadezimal
00
01
...
15
128
129
...
142
Note: The lightscene settings are also stored in the DALI Gateway after
a bus voltage or supply voltage failure. If a ballast should be replaced, the
lightscenes are immediately available again without further commissioning.
00h
Recall scene 1
01h
Recall scene 2
...
0EH
Recall scene 16
80h
81h
...
8EH
Store scene 16
Meaning
...
Store scene 1
Store scene 2
...