Feedback Status Behaviour - ABB DG/S 1.1 Product Manual

I-bus eib / knx dali-gateway
Table of Contents

Advertisement

®
ABB i-bus
EIB
A.5
Feedback status
behaviour
© 2006 ABB STOTZ-KONTAKT GmbH
Appendix
The following table provides a simple overview of when feedback objects are
sent. They depend on the state of the output and the received command.
With the "Switch/Status" object, it is also possible to set whether
transmission is continuously on or only after a change.
"–" means that the feedback object is not sent.
Switch object "Switch/Status"
Old state
Received
command
OFF command
OFF
DIM command
OFF
VALUE command
OFF
Scene command
OFF
OFF command
OFF
DIM command
OFF
OFF
VALUE command
OFF
Scene command
ON
OFF command
ON
DIM command
ON
VALUE command
ON
Scene command
ON
OFF command
ON
DIM command
ON
VALUE command
ON
Scene command
Switch object "Brightness value/Status"
Old state
Received
command
OFF command
OFF
DIM command
OFF
VALUE command
OFF
Scene command
OFF
OFF command
OFF
DIM command
OFF
OFF
VALUE command
OFF
Scene command
ON / x%
OFF command
ON / x%
DIM command
ON / x%
VALUE command
ON / x%
Scene command
ON / x%
OFF command
ON / x%
DIM command
ON / x%
VALUE command
ON / x%
Scene command
ON
OFF command
ON
DIM command
ON
VALUE command
ON
Scene command
New state
Switch feedback content
"always
send"
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
OFF
OFF
Min. Dimm
ON
OFF
OFF
OFF
OFF
New state
Switch feedback content
"always
send"
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON / y%
y %
ON / y%
y %
ON / y%
y %
ON / y%
y %
ON / x%
x%
ON / x%
x%
ON / x%
x%
ON / x%
x%
ON / y%
y %
ON / y%
y %
ON / y%
y %
ON / y%
y %
OFF
0%
Min. Dim
Min. Dim %
OFF
0%
OFF
0%
"send
on
change"
-
-
-
-
ON
ON
ON
ON
-
-
-
-
OFF
-
OFF
OFF
"send
on
change"
-
-
-
-
y %
y %
y %
y %
-
-
-
-
y %
y %
y %
y %
0%
Min. Dim %
0%
0%
98