ABB DG/S 1.1 Product Manual page 61

I-bus eib / knx dali-gateway
Table of Contents

Advertisement

®
ABB i-bus
EIB / KNX
© 2006 ABB STOTZ-KONTAKT GmbH
Functional description
With these 1-byte communication objects, lightscenes can be stored
individually e.g. with a push button or another operating device.
Fig. 20
Communication objects for "Lightscenes 1...15"
No.
Function
52
Control scenes
Lightscenes 1 ... 15 Control scenes [Non EIS; 8-bit coded]: All 15 scenes can be
controlled via this 1-byte communication object using a coded telegram. The number of the
addressed scene is received via a telegram together with the information about whether the
scene should be retrieved or the current scene should be stored (if permitted).
Telegram format (1 byte):
EIB / KNX 1-byte telegram
value
00 or 64
01 or 65
02 or 66
...
14 or 78
128 or 192
128 or 193
130 or 184
...
191 or 206
The exact code table for 8-bit scene telegrams can be seen in the appendix.
An example of an 8-bit scene is described in section 5.1 "Application and planning".
Table 11
Communication objects for "Lightscenes 1...15"
Object name
Lightscenes 1 ... 15
MXSSSSSS
(MSB) (LSB)
M:
0 – scene is retrieved
1 – scene is stored (if allowed)
X:
not used
S:
Number of the scene (1 ... 15 as 8-bit value)
Meaning
Retrieve scene 1
Retrieve scene 2
Retrieve scene 3
...
Retrieve scene 15
Store scene 1
Store scene 2
Store scene 3
...
Store scene 15
Data type
Flags
8 bit
C, W
(Non EIS)
DPT
18.001