3.5.3
Lightscene communication
objects
© 2006 ABB STOTZ-KONTAKT GmbH
Functional description
Fig. 18
Communication objects for "Recall Lightscene x/y"
15 lightscenes can be activated via the parameter setting. The scenes can
be defined by the ETS entries or set individually by the user according to
personal requirements via the individual object. It is possible for each scene
to disable overwriting of the brightness values during an ETS download. The
individually set brightness values of the lightscene are hereby retained
during an ETS download.
There are separate communication objects for retrieving or saving the 15
lightscenes. There is a further 8-bit communication object available, with
which each one of the 15 lightscenes can be stored or retrieved via an 8-bit
code.
No.
Function
36
Recall scene
37
Recall scene
38
Recall scene
39
Recall scene
40
Recall scene
41
Recall scene
42
Recall scene
43
Recall scene
Lightscene X/Y Recall scene [EIS 1; 1-bit switching]: The scenes are retrieved via this
object. On receipt of a telegram, channels which are assigned to the scene are set to the
stored or parameterised brightness values. The communication objects are only visible if the
scenes have been activated in the Scenes parameter window. The scene can consist of
devices from channel A and B.
Telegram value
"0": Recall scene X
"1": Recall scene Y
Table 9
Communication objects for "Recall Lightscene x/y""
Object name
Data type
Scene 1/2
1 bit (EIS 1)
DPT 1.022
Scene 3/4
1 bit (EIS 1)
DPT 1.022
Scene 5/6
1 bit (EIS 1)
DPT 1.022
Scene 7/8
1 bit (EIS 1)
DPT 1.022
Scene 9/10
1 bit (EIS 1)
DPT 1.022
Scene 11/12
1 bit (EIS 1)
DPT 1.022
Scene 13/14
1 bit (EIS 1)
DPT 1.022
Scene 15
1 bit (EIS 1)
DPT 1.022
Flags
C, W
C, W
C, W
C, W
C, W
C, W
C, W
C, W
55