T EC HN IC A L D O CUM E NT
ABB Ability™ Smart Sensor gateway
Installation manual
DOCUMENT ID
9AKK107046A4620
© Copyright 2020 ABB. All rights reserved.
REV.
G
DATE
April 2020
LANG.
PAGE
EN
1/17

Advertisement

Table of Contents
loading

Summary of Contents for ABB Ability Smart Sensor Gateway

  • Page 1 — T EC HN IC A L D O CUM E NT ABB Ability™ Smart Sensor gateway Installation manual DOCUMENT ID REV. DATE LANG. PAGE 9AKK107046A4620 April 2020 1/17 © Copyright 2020 ABB. All rights reserved.
  • Page 2: Table Of Contents

    WIFI connection ......................11 USB mobile dongle connection ................... 12 Firewall configuration ....................13 Verifying the configuration ..................14 3 TROUBLESHOOTING ................. 15 DOCUMENT ID REV. DATE LANG. PAGE 9AKK107046A4620 April 2020 2/17 © Copyright 2020 ABB. All rights reserved.
  • Page 3: General

    AB B A BIL IT Y™ S M ART S EN SO R G AT EWAY General The ABB Ability™ Smart Sensor gateway is used to upload the Smart Sensor data automatically to the Smart Sensor portal. The gateway needs to be configured for Internet access before it can start reading the Smart Sensors.
  • Page 4: Installation

    Mobile network needs to have adequate signal strength. In most demanding locations, an extension USB cable or external antenna might be needed for USB modem/dongle. DOCUMENT ID REV. DATE LANG. PAGE 9AKK107046A4620 April 2020 4/17 © Copyright 2020 ABB. All rights reserved.
  • Page 5: Recommended Location

    If the gateway has trouble connecting to a specific Smart Sensor, it is recommended to rotate the gateway to point in that direction. DOCUMENT ID REV. DATE LANG. PAGE 9AKK107046A4620 April 2020 5/17 © Copyright 2020 ABB. All rights reserved.
  • Page 6: Gateway Configuration

    AC (Access Controller) server. If no time is shown, it means that the gateway does not have a connection to the AC server. AC server connection is needed for the Smart Sensor data transfer. DOCUMENT ID REV. DATE LANG. PAGE 9AKK107046A4620 April 2020 6/17 © Copyright 2020 ABB. All rights reserved.
  • Page 7 Connection Priority is where a priority connection method is selected in case there are several in use. Select the priority according to connection in use: Wired for PoE and LAN connections. Wireless for WIFI connection. DOCUMENT ID REV. DATE LANG. PAGE 9AKK107046A4620 April 2020 7/17 © Copyright 2020 ABB. All rights reserved.
  • Page 8 AB B A BIL IT Y™ S M ART S EN SO R G AT EWAY 3G/4G for mobile USB dongle connection. Figure 4 Basic page DOCUMENT ID REV. DATE LANG. PAGE 9AKK107046A4620 April 2020 8/17 © Copyright 2020 ABB. All rights reserved.
  • Page 9: Poe Connection

    Connection Priority: Wired IP Allocation: DHCP or Static (in case the IP allocation is given) Press Apply at the bottom of the screen. DOCUMENT ID REV. DATE LANG. PAGE 9AKK107046A4620 April 2020 9/17 © Copyright 2020 ABB. All rights reserved.
  • Page 10: Lan/Ethernet Cable Connection

    Connection Priority: Wired IP Allocation: DHCP or Static (in case the IP allocation is given) Press Apply at the bottom of the screen. DOCUMENT ID REV. DATE LANG. PAGE 9AKK107046A4620 April 2020 10/17 © Copyright 2020 ABB. All rights reserved.
  • Page 11: Wifi Connection

    Press the reset button at the bottom of the gateway for 10 seconds to reset the gateway to factory default values. DOCUMENT ID REV. DATE LANG. PAGE 9AKK107046A4620 April 2020 11/17 © Copyright 2020 ABB. All rights reserved.
  • Page 12: Usb Mobile Dongle Connection

    If a WIFI modem is used, insert the modem to USB port at the bottom of the gateway and follow the 2.6 WIFI connection section instructions. DOCUMENT ID REV. DATE LANG. PAGE 9AKK107046A4620 April 2020 12/17 © Copyright 2020 ABB. All rights reserved.
  • Page 13: Firewall Configuration

    Firewall should allow communication between the gateway and Access Controller, and gateway and Smart Sensor platform respectively (see required ports in section 2.1 Prerequisites for Installation). DOCUMENT ID REV. DATE LANG. PAGE 9AKK107046A4620 April 2020 13/17 © Copyright 2020 ABB. All rights reserved.
  • Page 14: Verifying The Configuration

    Reboot the gateway (power off/on) Connection to Access controller can be verified also with Debug Tools in Other tab: abb.cassia.pro, Time 5s and press Start. To check connection to Access Control- ler, select Ping, add Address abb.cassia.pro (or gw.smartsensor.abb.com.cn in case of China).
  • Page 15: Troubleshooting

    Basic Page. Change the mode from “AC Managed Router” to “Standalone Router”. Gateway will automatically reboot and is operational again within 30 to 60 seconds. DOCUMENT ID REV. DATE LANG. PAGE 9AKK107046A4620 April 2020 15/17 © Copyright 2020 ABB. All rights reserved.
  • Page 16 RSSI value between 0 and -70 is OK RSSI value between -70 and -80 is weak, sensor might be read time to time DOCUMENT ID REV. DATE LANG. PAGE 9AKK107046A4620 April 2020 16/17 © Copyright 2020 ABB. All rights reserved.
  • Page 17 If the desired Smart Sensors are showing RSSI values of -70 or less, it is recommended to adjust the gateway’s location or orientation. For more support, please contact Smart Sensor support: support.smartsensor@abb.com DOCUMENT ID REV. DATE LANG. PAGE 9AKK107046A4620 April 2020 17/17 © Copyright 2020 ABB. All rights reserved.