ID61/62 Series Panel - Installation, Commissioning & Configuration Manual
Output No. Type
1 (B01)
Fixed Monitored
Output Circuit (A)
2 (B02)
Fixed Monitored
Output Circuit (B)
3 (B03)
Hardware Configurable
CFG Output Circuit (C)
4 (B04)
Hardware Configurable
CFG Output Circuit (D)
5 (B05)
-VE Output Circuit (1)
6 (B06)
-VE Output Circuit (2)
2

5.6.3 On-Board Circuits

This option permits configuration of the On-Board Output
Circuits. There are six output circuits as defined in the
following table.
Description
Monitored Sounder (SDR or SDH) or Monitored Control
Module (CTL) or Transmission Device (TxD) can be
programmed for Fire Alarm, Fault, Pre-Alarm, Plant
Warning or Extinguishing System CBE Rules.
Factory Default = Fire Alarm - All Zones.
Monitored Sounder (SDR or SDH) or Monitored Control
Module (CTL) can be programmed for Fire Alarm, Fault,
Pre-Alarm, Plant Warning or Extinguishing System CBE
Rules.
Factory Default = Fire Alarm - All Zones.
Can be configured for operation as a Monitored Output
(Sounder Circuit or Relay Circuit) or as an Unmonitored
Output (volt-free style relay Circuit).
Can be programmed for Fire Alarm, Fault, Pre-Alarm,
Plant Warning or Extinguishing System CBE Rules.
Factory Default = Unmonitored Relay.
Can be configured for operation as a Monitored Output
(Sounder Circuit or Relay Circuit) or as an Unmonitored
Output (dry-contact style relay Circuit).
Can be programmed for Fire Alarm, Fault, Pre-Alarm,
Plant Warning or Extinguishing System CBE Rules.
Factory Default = Unmonitored Relay.
Unmonitored Output Circuit. Can be programmed for Fire
Alarm, Fault, Pre-Alarm, Plant Warning or Extinguishing
System CBE Rules.
This output is normally used to drive an external relay.
Factory Default = General Pre-Alarm
Unmonitored Output Circuit. Can be programmed for Fire
Alarm, Fault, Pre-Alarm, Plant Warning or Extinguishing
System CBE Rules.
This output is normally used to drive an external relay.
Factory Default = Plant Warning
To change the On-Board Output CBE rule:
1 Press '
' on the numeric keypad, select the
2
On-Board menu from the Circuit Menu below.
[S1 Circuit]
1 : SLC Loop 2 : On-Board
2 The display then shows the following menu. Select
the appropriate action:
[ON-BOARD]
B01 (SDR)
1 : Type
2 : CBE Rule (01)
a. Using the numeric keypad press '
Type of output, or
b. Press '
' on the numeric keypad to change the CBE
2
Rule with which the On-board output is associated.
c. Use the '
/
2
8
number and its associated CBE Rule.
d. Press the '
' on the numeric keypad to toggle the monitoring
3
end-of-line device type: resistor (default setting) or diode.
e. Press the '
' to Cancel and return to the Circuit
4
menu.
77
3: Mon. : RES.
: Change < : Exit
' to change the
1
' to change the On-board output
997-457-000-8, Issue 8