52 Rack-mount and ground PRI Gateway components
Step
1
2
3

Ground a PRI Gateway

Perform the steps in
(page
Procedure 2
Grounding PRI Gateway components
Step
1
2
3
Media Gateway 1000E PRI Gateway Installation and Commissioning
Action
Slide the PRI Gateway into the rack. Make sure it is supported.
Use the four screws to fasten the PRI Gateway to the rack.
Ground the PRI Gateway. See
Gateway components" (page
Procedure 2 "Grounding PRI Gateway components"
52).
WARNING
Only a qualified person must make the connection in the AC
electrical panel.
Action
Disconnect the AC power cord from the power outlet.
Install a #6 - #10 AWG ground wire from the ground lug at the
back of the PRI Gateway to the ground bar/frame ground bar.
Place a tag marked DO NOT DISCONNECT on the ground wire
at the electrical panel.
Nortel Communication Server 1000
NN43041-311 04.01 4 June 2010
Copyright © 2007-2010 Nortel Networks. All Rights Reserved.
Procedure 2 "Grounding PRI
52).
--End--
--End--