Ground A Pri Gateway - Nortel Media Gateway 1000E PRI Installation And Comissioning Manual

Hide thumbs Also See for Media Gateway 1000E PRI:
Table of Contents

Advertisement

46 Rack-mount and ground PRI Gateway components
Procedure 1
Rack-mounting a PRI Gateway
Step
1
2
3

Ground a PRI Gateway

Follow the steps in
(page
Procedure 2
Grounding PRI Gateway components
Step
1
2
3
Media Gateway 1000E PRI Gateway Installation and Commissioning
Copyright © 2007, Nortel Networks
.
Action
Slide the PRI Gateway into the rack. Make sure it is supported.
Use the four screws to fasten the PRI Gateway to the rack.
Ground the PRI Gateway. See
Gateway components" (page
Procedure 2 "Grounding PRI Gateway components"
46).
WARNING
Only a qualified person must make the connection in the AC
electrical panel.
Action
Disconnect the AC power cord from the power outlet.
Install a #6 - #10 AWG ground wire from the ground lug at the back
of the PRI Gateway to the ground bar/frame ground bar.
Place a tag marked DO NOT DISCONNECT on the ground wire at
the electrical panel.
Nortel Communication Server 1000
NN43041-311 01.01 Standard
Release 5.0 30 May 2007
Procedure 2 "Grounding PRI
46).
—End—
—End—

Advertisement

Table of Contents
loading

Table of Contents