5.5.5 Limit of Inertia Ratio

Please see the limit of inertia ratio below during the estimation.
Acceleration / Deceleration time of reaching 2000 r/min should be less than 1 second.
The speed in forward and reverse direction should be higher than 200 r/min.
The load inertia should be under 100 times of motor inertia.
The change of external force of inertia ratio cannot be too severe.
In auto mode, the inertia value will be saved to P1-37 every 30 minutes; while in semi-auto mode,
the inertia value will be saved to P1-37 only until the system inertia is stable and stops the
estimation of load inertia.
1. Lower the value of P2-31 to reduce the noise.
2. If not desire to lower the value of P2-31, value
of P2-23 and P2-24 can be used to suppress the
resonance as well.
(Please refer to Chapter 5.6.6)
September, 2015
Servo off and set P2-32 to 2. Then, Servo on
again.
Set P0-02 to 15. The panel
displays The inertia ratio*.
The servo drive issues the
command and to make motor
alternately accelerate /
decelerate.
Yes
Any
resonance?
The inertia ratio shown on
the panel is stable.
Satisfactory
performance?
If the value of inertia ratio
remains almost the same, then
servo off and set P2-32 to 0.
Complete
Figure 5-5 Estimation of load inertia
Trial Operation and Tuning
No
No
Yes
Increase the value of P2-31
No
to increase response and
stiffness.
Yes
Yes
5
5-15