Programming
6.5 Readout and Programming of Indexed
Parameters
Select the parameter, press [OK], and press [
through the indexed values. To change the parameter
value, select the indexed value and press [OK]. Change the
value by pressing [
]/[
]. Press [OK] to accept the new
setting. Press [Cancel] to abort. Press [Back] to leave the
parameter.

6.6 Initialization to Default Settings

There are 2 ways to initialize the frequency converter to
the default settings.
Recommended initialization
1.
Select parameter 14-22 Operation Mode.
2.
Press [OK].
3.
Select [2] Initialisation and Press [OK].
4.
Power off the frequency converter and wait until
the display turns off.
5.
Reconnect the mains supply. The frequency
converter is now reset, except for the following
parameters:
Parameter 1-06 Clockwise Direction
Parameter 8-30 Protocol
Parameter 8-31 Address
Parameter 8-32 Baud Rate
Parameter 8-33 Parity / Stop Bits
Parameter 8-35 Minimum Response Delay
Parameter 8-36 Maximum Response Delay
Parameter 8-37 Maximum Inter-char delay
Parameter 8-70 BACnet Device Instance
Parameter 8-72 MS/TP Max Masters
Parameter 8-73 MS/TP Max Info Frames
Parameter 8-74 "I am" Service
Parameter 8-75 Intialisation Password
Parameter 15-00 Operating hours to
parameter 15-05 Over Volt's
Parameter 15-03 Power Up's
Parameter 15-04 Over Temp's
Parameter 15-05 Over Volt's
Parameter 15-30 Alarm Log: Error Code
Parameter group 15-4* Drive identification
Parameter 18-10 FireMode Log:Event
MG18C702
Design Guide
2-finger initialization
The other way to initialize the frequency converter to
default settings is through 2-finger initialization:
1.
]/[
] to scroll
2.
3.
4.
Initialization of parameters is confirmed by alarm 80, Drive
initialised in the display after the power cycle.
Danfoss A/S © 04/2016 All rights reserved.
Power off the frequency converter.
Press [OK] and [Menu].
Power up the frequency converter while still
pressing the keys for 10 s.
The frequency converter is now reset, except for
the following parameters:
Parameter 1-06 Clockwise Direction
Parameter 15-00 Operating hours
Parameter 15-03 Power Up's
Parameter 15-04 Over Temp's
Parameter 15-05 Over Volt's
Parameter group 15-4* Drive identification
Parameter 18-10 FireMode Log:Event
6
6
79

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vlt fc 101

Table of Contents