General Specifications
2) Terminals 42 and 45 can also be programmed as analog output.
The digital outputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.

8.4.8 Control Card, RS485 Serial Communication

Terminal number
Terminal number

8.4.9 Control Card, 24 V DC Output

Terminal number
Maximum load

8.4.10 Relay Output

Programmable relay output
Relay 01 and 02
Maximum terminal load (AC-1)
Maximum terminal load (AC-15)
Maximum terminal load (DC-1)
Maximum terminal load (DC-13)
Maximum terminal load (AC-1)
Maximum terminal load (AC-15)
Maximum terminal load (DC-1)
Minimum terminal load on 01–03 (NC), 01–02 (NO)
Environment according to EN 60664-1
1) IEC 60947 parts 4 and 5.

8.4.11 Control Card, 10 V DC Output

Terminal number
Output voltage
Maximum load

8.4.12 Ambient Conditions

Enclosure protection rating
Enclosure kit available
Vibration test
Maximum relative humidity
Aggressive environment (IEC 60721-3-3), coated (standard) enclosure sizes H1–H5
Aggressive environment (IEC 60721-3-3), non-coated enclosure sizes H6–H10
Aggressive environment (IEC 60721-3-3), coated (optional) enclosure sizes H6–H10
Aggressive environment (IEC 60721-3-3), non-coated enclosure sizes I2–I8
Test method according to IEC 60068-2-43 H2S (10 days)
Ambient temperature
Minimum ambient temperature during full-scale operation
Minimum ambient temperature at reduced performance, enclosure sizes H1–H5 and I2–I4
Minimum ambient temperature at reduced performance, enclosure sizes H6–H10 and I6–I8
Temperature during storage/transport
Maximum altitude above sea level without derating
Maximum altitude above sea level with derating
MG18C702
Design Guide
1)
on 01–02/04–05 (NO) (resistive load)
on 01–02/04–05 (NO) (inductive load @ cosφ 0.4)
1)
1)
on 01–02/04–05 (NO) (resistive load)
1)
on 01–02/04–05 (NO) (inductive load)
1)
on 01–03/04–06 (NC) (resistive load)
on 01–03/04–06 (NC) (inductive load @ cosφ 0.4)
1)
1)
on 01–03/04–06 (NC) (resistive load)
5–95% (IEC 60721-3-3; Class 3K3 (non-condensing) during operation
See maximum output current at 40/50 °C (104/122°F) in chapter 8.2.2 3x380–480 V AC.
Danfoss A/S © 04/2016 All rights reserved.
68 (P, TX+, RX+), 69 (N, TX-, RX-)
61 common for terminals 68 and 69
01–03 (NC), 01–02 (NO), 04–06 (NC), 04–05 (NO)
24 V DC 10 mA, 24 V AC 20 mA
Overvoltage category III/pollution degree 2
-30 to +65/70 °C (-22 to +149/158°F)
12
80 mA
2
250 V AC, 3 A
250 V AC, 0.2 A
8
8
30 V DC, 2 A
24 V DC, 0.1 A
250 V AC, 3 A
250 V AC, 0.2 A
30 V DC, 2 A
50
10.5 V ±0.5 V
25 mA
IP20, IP54
IP21, TYPE 1
1.0 g
Class 3C3
Class 3C2
Class 3C3
Class 3C2
0 °C (32 °F)
-20 °C (-4 °F)
-10 °C (14 °F)
1000 m (3281 ft)
3000 m (9843 ft)
115