General Specifications

8.4 General Technical Data

Protection and features
Electronic motor thermal protection against overload.
Temperature monitoring of the heat sink ensures that the frequency converter trips if there is overtemperature.
The frequency converter is protected against short circuits between motor terminals U, V, W.
When a motor phase is missing, the frequency converter trips and issues an alarm.
When a mains phase is missing, the frequency converter trips or issues a warning (depending on the load).
Monitoring of the DC-link voltage ensures that the frequency converter trips when the DC-link voltage is too low
or too high.
The frequency converter is protected against ground faults on motor terminals U, V, W.

8.4.1 Mains Supply (L1, L2, L3)

Supply voltage
Supply voltage
Supply voltage
Supply frequency
Maximum imbalance temporary between mains phases
True power factor (λ)
Displacement power factor (cosφ) near unity
Switching on the input supply L1, L2, L3 (power-ups) enclosure sizes H1–H5, I2, I3, I4
Switching on the input supply L1, L2, L3 (power-ups) enclosure sizes H6–H8, I6–I8
Environment according to EN 60664-1
The unit is suitable for use on a circuit capable of delivering not more than 100000 A
maximum.

8.4.2 Motor Output (U, V, W)

Output voltage
Output frequency
Switching on output
Ramp times

8.4.3 Cable Length and Cross-section

Maximum motor cable length, shielded/armored (EMC-correct installation)
Maximum motor cable length, unshielded/unarmored
Maximum cross-section to motor, mains
Cross-section DC terminals for filter feedback on enclosure sizes H1–H3, I2, I3, I4
Cross-section DC terminals for filter feedback on enclosure sizes H4–H5
Maximum cross-section to control terminals, rigid wire
Maximum cross-section to control terminals, flexible cable
Minimum cross-section to control terminals
1) See chapter 8.2.2 3x380–480 V AC for more information.
MG18C702
Design Guide
1)
Danfoss A/S © 04/2016 All rights reserved.
200–240 V ±10%
380–480 V ±10%
525–600 V ±10%
3.0% of rated supply voltage
≥0.9 nominal at rated load
Maximum 2 times/minute
Maximum 1 time/minute
Overvoltage category III/pollution degree 2
symmetrical Amperes, 240/480 V
rms
0–100% of supply voltage
+
0–200 Hz (VVC
), 0–400 Hz (u/f )
See chapter 3.4.3 EMC Emission Test Results
4 mm
16 mm
2.5 mm
2.5 mm
0.05 mm
50/60 Hz
8
8
(>0.98)
Unlimited
0.05–3600 s
50 m (164 ft)
2
/11 AWG
2
/6 AWG
2
/14 AWG
2
/14 AWG
2
/30 AWG
113