Emission Requirements - Danfoss VLT HVAC Basic Drive FC 101 Design Manual

Hide thumbs Also See for VLT HVAC Basic Drive FC 101:
Table of Contents

Advertisement

Product Overview
level alongside motor and brake cables. Radio interference
higher than 50 MHz (airborne) is especially generated by
the control electronics.
z
L1
z
L2
z
L3
z
PE
PE
3
1
Ground wire
4
Frequency converter
Illustration 3.52 Generation of Leakage Currents

3.4.2 Emission Requirements

The EMC product standard for frequency converters
defines 4 categories (C1, C2, C3, and C4) with specified
requirements for emission and immunity. Table 3.5 states
the definition of the 4 categories and the equivalent classi-
fication from EN 55011.
MG18C702
Design Guide
C
S
U
I
1
V
W
I
2
I
3
C
S
I
4
4
2
Shield
5
Shielded motor cable
Danfoss A/S © 04/2016 All rights reserved.
C
S
1
2
I
4
5
3
AC mains supply
6
Motor
EN/IEC
61800-3
Definition
Category
Frequency converters installed in
the first environment (home and
C1
office) with a supply voltage less
than 1000 V.
Frequency converters installed in
the first environment (home and
office) with a supply voltage less
C2
than 1000 V, which are neither
plug-in nor movable and are
intended to be installed and
commissioned by a professional.
Frequency converters installed in
the second environment (industrial)
C3
with a supply voltage lower than
1000 V.
Frequency converters installed in
the second environment with a
supply voltage equal to or above
C4
1000 V or rated current equal to or
above 400 A or intended for use in
complex systems.
Table 3.5 Correlation between IEC 61800-3 and
EN 55011
C
S
C
C
S
S
6
Equivalent
emission class
in EN 55011
Class B
Class A Group 1
Class A Group 2
No limit line.