CD that is shipped with the waste. product, or in print at the local Danfoss sales office. It must be separately collected with electrical MCT 10 Set-up Software support and electronic waste according to local and Download the software from www.danfoss.com/Busines-...
Page 19
10000 A Short-circuit protection (symmetrical), 480 V maximum. Danfoss recommends using the fuses and circuit breakers listed in Table 3.7 to protect service personnel or other NOTICE equipment in case of an internal failure in the unit or a In the event of malfunction, failure to follow the short circuit on the DC link.
Discharge from output phases to ground, using the value of Earth Fault – parameter 15-31 Alarm Log Value if possible. Control Voltage – Fault Control voltage is low. Contact the local Danfoss supplier. 24 V supply low 24 V DC supply may be overloaded. AMA calibration – – failed Contact the local Danfoss supplier.
Page 44
The control card and power card are not matched. Illegal power – section configu- – ration Internal fault. Contact the local Danfoss supplier. Drive initialised – – All parameter settings are initialized to default settings. Auto DC Braking –...
1) Applies for dimensioning of frequency converter cooling. If the switching frequency is higher than the default setting, the power losses may increase. LCP and typical control card power consumptions are included. For power loss data according to EN 50598-2, refer to www.danfoss.com/ vltenergyefficiency.
1) Applies for dimensioning of frequency converter cooling. If the switching frequency is higher than the default setting, the power losses may increase. LCP and typical control card power consumptions are included. For power loss data according to EN 50598-2, refer to www.danfoss.com/ vltenergyefficiency.
Page 47
1) Applies for dimensioning of frequency converter cooling. If the switching frequency is higher than the default setting, the power losses may increase. LCP and typical control card power consumptions are included. For power loss data according to EN 50598-2, refer to www.danfoss.com/ vltenergyefficiency.
Page 48
1) Applies for dimensioning of frequency converter cooling. If the switching frequency is higher than the default setting, the power losses may increase. LCP and typical control card power consumptions are included. For power loss data according to EN 50598-2, refer to www.danfoss.com/ vltenergyefficiency.
Page 49
1) Applies for dimensioning of frequency converter cooling. If the switching frequency is higher than the default setting, the power losses may increase. LCP and typical control card power consumptions are included. For power loss data according to EN 50598-2, refer to www.danfoss.com/ vltenergyefficiency.
1) Applies for dimensioning of frequency converter cooling. If the switching frequency is higher than the default setting, the power losses may increase. LCP and typical control card power consumptions are included. For power loss data according to EN 50598-2, refer to www.danfoss.com/ vltenergyefficiency.
6.2.1 Derating for Ambient Temperature pressure. For altitudes above 2000 m (6562 ft), contact and Switching Frequency Danfoss regarding PELV. Below 1000 m (3281 ft) altitude, derating is not necessary. For altitudes above 1000 m Ensure that the ambient temperature measured over 24 (3281 ft), decrease the ambient temperature or the hours is at least 5 °C (41 °F) lower than the maximum...
Page 56
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed. All trademarks in this material are property of the respective companies.