General Specifications
8 General Specifications
8.1 Mechanical Dimensions
8.1.1 Side-by-side Installation
The frequency converter can be mounted side-by-side but requires the clearance above and below for cooling.
Size
IP class
H1
H2
H3
H4
H5
H6
H7
H8
8
8
H9
H10
I2
I3
I4
I6
I7
I8
Table 8.1 Clearance Required for Cooling
NOTICE
With IP21/NEMA Type1 option kit mounted, a distance of 50 mm (2 in) between the units is required.
100
3x200–240 V
IP20
0.25–1.5 (0.33–2)
IP20
2.2 (3)
IP20
3.7 (5)
IP20
5.5–7.5 (7.5–10)
IP20
11 (15)
IP20
15–18.5 (20–25)
IP20
22–30 (30–40)
IP20
37–45 (50–60)
IP20
–
IP20
–
IP54
–
IP54
–
IP54
–
IP54
–
IP54
–
IP54
–
Danfoss A/S © 04/2016 All rights reserved.
®
VLT
HVAC Basic Drive FC 101
Power [kW (hp)]
3x380–480 V
0.37–1.5 (0.5–2)
2.2–4 (3–5)
5.5–7.5 (7.5–10)
11–15 (15–20)
18.5–22 (25–30)
30–45 (40–60)
18.5–30 (25–40)
55–75 (70–100)
90 (125)
75–90 (100–125)
–
–
0.75–4.0 (1–5)
5.5–7.5 (7.5–10)
11–18.5 (15–25)
22–37 (30–50)
45–55 (60–70)
75–90 (100–125)
Clearance above/below [mm (in)]
3x525–600 V
–
–
–
–
–
37–55 (50–70)
2.2–7.5 (3–10)
11–15 (15–20)
–
–
–
–
–
–
100 (4)
100 (4)
100 (4)
100 (4)
100 (4)
200 (7.9)
200 (7.9)
225 (8.9)
100 (4)
200 (7.9)
100 (4)
100 (4)
100 (4)
200 (7.9)
200 (7.9)
225 (8.9)
MG18C702