Danfoss VLT HVAC Basic Drive FC 101 Design Manual page 43

Hide thumbs Also See for VLT HVAC Basic Drive FC 101:
Table of Contents

Advertisement

Product Overview
Individual harmonic current I
I
5
Actual 0.37–22
kW (0.5–30 hp),
36.7
IP20, 380–480 V
(typical)
≥120
Limit for R
40
sce
Harmonic current distortion factor (%)
THDi
Actual 0.37–22
kW (0.5–30 hp),
44.4
380–480 V
(typical)
≥120
Limit for R
48
sce
Table 3.11 Harmonic Current 0.37–22 kW (0.5–30 hp), 380-480 V
Individual harmonic current I
I
5
Actual 30–90 kW
(40–120 hp),
36.7
IP20, 380–480 V
(typical)
≥120
Limit for R
40
sce
Harmonic current distortion factor (%)
THDi
Actual 30–90 kW
(40–120 hp), 380–
40.6
480 V (typical)
≥120
Limit for R
48
sce
Table 3.12 Harmonic Current 30–90 kW (40–120 hp), 380–480 V
Individual harmonic current I
I
5
Actual 2.2–15 kW
(3–20 hp), IP20,
48
525–600 V
(typical)
Harmonic current distortion factor (%)
THDi
Actual 2.2–15 kW
(3–20 hp), 525–
55
600 V (typical)
Table 3.13 Harmonic Current 2.2–15 kW (3–20 hp), 525–600 V
MG18C702
Design Guide
/I
(%)
n
1
I
I
I
7
11
13
20.8
7.6
6.4
25
15
10
PWHD
40.8
46
/I
(%)
n
1
I
I
I
7
11
13
13.8
6.9
4.2
25
15
10
PWHD
28.8
46
/I
(%)
n
1
I
I
I
7
11
13
25
7
5
PWHD
27
Danfoss A/S © 04/2016 All rights reserved.
Individual harmonic current I
I
5
Actual 18.5–90
kW (25–120 hp),
48.8
IP20, 525–600 V
(typical)
Harmonic current distortion factor (%)
THDi
Actual 18.5–90
kW (25–120 hp),
55.7
525–600 V
(typical)
Table 3.14 Harmonic Current 18.5–90 kW (25–120 hp), 525–600 V
Individual harmonic current I
I
5
Actual 22–90 kW
(30–120 hp),
36.3
IP54, 400 V
(typical)
≥120
Limit for R
40
sce
Harmonic current distortion factor (%)
THDi
Actual 22–90 kW
(30–120 hp), IP54
40.1
400 V (typical)
≥120
Limit for R
48
sce
Table 3.15 Harmonic Current 22–90 kW (30–120 hp), 400 V
Individual harmonic current I
I
5
Actual 0.75–18.5
kW (1–25 hp),
36.7
IP54, 380-480 V
(typical)
≥120
Limit for R
40
sce
Harmonic current distortion factor (%)
THDi
Actual 0.75–18.5
kW (1–25 hp),
44.4
IP54, 380–480 V
(typical)
≥120
Limit for R
48
sce
Table 3.16 Harmonic Current 0.75–18.5 kW (1–25 hp), 380–480 V
/I
(%)
n
1
I
I
I
7
11
13
24.7
6.3
5
PWHD
25.3
/I
(%)
n
1
I
I
I
7
11
13
14
7
4.3
25
15
10
PWHD
27.1
46
/I
(%)
n
1
I
I
I
7
11
13
20.8
7.6
6.4
25
15
10
PWHD
40.8
46
41
3
3

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vlt fc 101

Table of Contents