Output Signals - Siemens SITRANS FC620 Operating Instructions Manual

Coriolis flowmeters
Table of Contents

Advertisement

Transmitter
Fig. 84: Modbus connection

13.4.1.3 Output signals

Galvanic isolation
All circuits for inputs, outputs and power supply are galvanically isolated from each other.
Active current
One or two current outputs are available depending on order code position -Z.
output lout
Depending on the measured value, the active current output delivers 4 – 20 mA.
It may be used for output of the following measured values:
▪ Flow rate (mass, volume, net partial component flow of a mixture)
▪ Density
▪ Temperature
▪ Pressure
▪ Concentration
For HART communication devices, it is supplied on the current output lout1. The current
output may be operated in compliance with the NAMUR NE43 standard.
Nominal output current
Maximum output current range
Load resistance
Load resistance for secure HART communication
SITRANS FC
Fig. 85: Active current output connection lout HART
Passive current
output lout
Nominal output current
Maximum output current range
External power supply
Load resistance for secure HART
communication
Load resistance at current output
Balanced Pair
SITRANS FC
Slave n
Iout+
Iout-
Receiver
Master
Pull Up
Common
LT: Line Termination
1
Value
4 – 20 mA
2.4 – 21.6 mA
10.5 – 32 V
DC
230 – 600 Ω
≤ 911 Ω
A5E52748375-AA, 2023/09
FC6x0
Wiring
Pull Down
Value
4 – 20 mA
2.4 – 21.6 mA
≤ 750 Ω
230 – 600 Ω
127 / 194

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sitrans fc640

Table of Contents