Cable Specifications; Control Input/Ouput And Control Data - Danfoss VLT HVAC Drive FC 102 Operating Instructions Manual

315-1400 kw
Hide thumbs Also See for VLT HVAC Drive FC 102:
Table of Contents

Advertisement

General Specifications
Minimum ambient temperature during full-scale operation
Minimum ambient temperature at reduced performance
Temperature during storage/transport
Maximum altitude above sea level without derating
Maximum altitude above sea level with derating
For more information on derating for high altitude, see the section on special conditions in the design guide.
EMC standards, Emission
EMC standards, Immunity
2)
Energy efficiency class
For more information, see the section on special conditions in the design guide.
2) Determined according to EN50598-2 at:
Rated load
90% rated frequency
Switching frequency factory setting
Switching pattern factory setting

7.3 Cable Specifications

Cable lengths and cross-sections
Maximum motor cable length, screened/armoured
Maximum motor cable length, unscreened/unarmoured
Maximum cross-section to motor, mains, load sharing and brake
Maximum cross-section to control terminals, rigid wire
Maximum cross-section to control terminals, flexible cable
Maximum cross-section to control terminals, cable with enclosed core
Minimum cross-section to control terminals
1) See chapter 7.5 Electrical Data for more information.

7.4 Control Input/Ouput and Control Data

Digital inputs
Programmable digital inputs
Terminal number
Logic
Voltage level
Voltage level, logic '0' PNP
Voltage level, logic '1' PNP
Voltage level, logic '0' NPN
Voltage level, logic '1' NPN
Maximum voltage on input
Input resistance, R
i
All digital inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
1) Terminals 27 and 29 can also be programmed as output.
Analog inputs
Number of analog inputs
Terminal number
Modes
Mode select
Voltage mode
Voltage level
Input resistance, R
i
MG11F502
Operating Instructions
EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6
1)
Danfoss A/S © 08/2014 All rights reserved.
EN 61800-3, EN 61000-6-3/4, EN 55011, IEC 61800-3
EN 61800-3, EN 61000-6-1/2,
1.5 mm
2
/16 AWG (2 x 0.75 mm
18, 19, 27
switches S201 and S202
switch S201/S202 = OFF (U)
0 °C
-10 °C
-25 to +65/70 °C
1000 m
3000 m
IE2
7
150 m
300 m
2
)
2
1 mm
/18 AWG
2
0.5 mm
/20 AWG
2
0.25 mm
4 (6)
1)
, 29
1)
, 32, 33,
PNP or NPN
0–24 V DC
<5 V DC
>10 V DC
>19 V DC
<14 V DC
28 V DC
approx. 4 kΩ
2
53, 54
voltage or current
0-10 V (scaleable)
approx. 10 kΩ
107
7