Danfoss VLT HVAC Drive FC 102 Operating Instructions Manual page 92

315-1400 kw
Hide thumbs Also See for VLT HVAC Drive FC 102:
Table of Contents

Advertisement

How to Programme
6-16 Terminal 53 Filter Time Constant
Range:
0.001 s
[0.001 - 10
*
s]
6-17 Terminal 53 Live Zero
6
6
Option:
[0]
Disabled
[1]
Enabled
*
6-20 Terminal 54 Low Voltage
Range:
0.07 V
[ 0 - par.
*
6-21 V]
6-21 Terminal 54 High Voltage
Range:
10 V
[ par. 6-20
*
- 10 V]
6-24 Terminal 54 Low Ref./Feedb. Value
Range:
0
[-999999.999 -
*
999999.999 ]
90
Operating Instructions
Function:
NOTICE
This parameter cannot be adjusted
while the motor is running.
Enter the filter time constant. This
constant is a first-order digital low-pass
filter time for suppressing electrical noise
in terminal 53. A high value improves
dampening, but also increases the delay
through the filter.
Function:
Disables the live zero monitoring, for example if
the analog outputs are used as part of a
decentral I/O system (i.e. if these are used to feed
a Building Management System with data, and
not as part of any control functions related to the
frequency converter).
Function:
Enter the low-voltage value. This analog
input scaling value should correspond to
the low reference/feedback value, set in
parameter 6-24 Terminal 54 Low Ref./Feedb.
Value.
Function:
Enter the high-voltage value. This analog
input scaling value should correspond to the
high reference/feedback value set in
parameter 6-25 Terminal 54 High Ref./Feedb.
Value.
Function:
Enter the analog input scaling value that
corresponds to the low voltage/low
current value set in
parameter 6-20 Terminal 54 Low Voltage
and 6-22 Terminal 54 Low Current.
Danfoss A/S © 08/2014 All rights reserved.
6-25 Terminal 54 High Ref./Feedb. Value
Range:
Function:
100
[-999999.999 -
Enter the analog input scaling value
*
999999.999 ]
that corresponds to the high voltage/
high current value set in
parameter 6-21 Terminal 54 High Voltage
and 6-23 Terminal 54 High Current.
6-26 Terminal 54 Filter Time Constant
Range:
Function:
NOTICE
0.001 s
[0.001 -
*
10 s]
This parameter cannot be adjusted
while the motor is running.
Enter the filter time constant. This is a
first-order digital low-pass filter time
constant for suppressing electrical noise in
terminal 54. A high time constant value
improves dampening but also increases
the time delay through the filter.
6-27 Terminal 54 Live Zero
Option:
Function:
Disables the live zero monitoring, for example if
the analog outputs are used as part of a
decentral I/O system (i.e. if these are used to feed
a Building Management System with data, and
not as part of any control functions related to the
frequency converter).
[0]
Disabled
[1]
Enabled
*
6-50 Terminal 42 Output
Option:
Function:
Select the function of terminal 42 as an
analog current output. A motor current
of 20 mA corresponds to I
[0]
No operation
[100] Output freq.
0–100 Hz, (0–20 mA)
0-100
[101] Reference Min-
Minimum reference - Maximum
Max
reference, (0–20 mA)
[102] Feedback +-200% -200% to +200% of 20-14 Maximum
Reference/Feedb., (0–20 mA)
[103] Motor cur. 0-Imax 0 - Inverter Max. Current (16-37 Inv.
Max. Current), (0-20 mA)
[104] Torque 0-Tlim
0 - Torque limit (4-16 Torque Limit
Motor Mode), (0-20 mA)
[105] Torque 0-Tnom
0 - Motor rated torque, (0-20 mA)
[106] Power 0-Pnom
0 - Motor rated power, (0-20 mA)
.
max
MG11F502