Rated Power - Danfoss VLT HVAC Drive FC 102 Operating Instructions Manual

315-1400 kw
Hide thumbs Also See for VLT HVAC Drive FC 102:
Table of Contents

Advertisement

Mechanical Installation
Enclosure size size
E1
315–450 kW at
400 V
(380–480 V)
450–630 kW at
690 V
(525–690 V)
IP
21, 54
NEMA
Type 1/Type 12
Shipping
Height
840
dimensions
Width
2197
[mm]
Depth
736
Height
2000
Width
600
Frequency
converter
Depth
494
dimensions
Max.
[mm]
weight
313
[kg]
Table 3.3 Mechanical Dimensions, Enclosure Sizes E and F

3.2.6 Rated Power

Enclosure size
IP
21/54
Enclosure
protection
NEMA
Type 1/Type 12
Normal overload
315–450 kW at 400 V
rated power -
(380–480 V)
110% overload
450–630 kW at 690 V
torque
(525-690 V)
Table 3.4 Rated Power, Enclosure Types E and F
NOTICE
The F enclosures are available in 4 different sizes, F1, F2, F3 and F4. The F1 and F2 consist of an inverter cabinet on the
right and rectifier cabinet on the left. The F3 and F4 have an extra options cabinet left of the rectifier cabinet. The F3 is
an F1 with an extra options cabinet. The F4 is an F2 with an extra options cabinet.
MG11F502
Operating Instructions
E2
315–450 kW at
500–710 kW at
400 V
(380–480 V)
450–630 kW at
710–900 kW at
690 V
(525–690 V)
00
Chassis
Type 1/Type 12
831
1705
736
1547
585
498
277
E1
E2
00
Chassis
315–450 kW at 400 V
(380–480 V)
450–630 kW at 690 V
(525–690 V)
Danfoss A/S © 08/2014 All rights reserved.
F1
F2
800–1000 kW at
400 V
400 V
(380–480 V)
(380–480 V)
1000–1200 kW at
690 V
690 V
(525–690 V)
(525–690 V)
21, 54
21, 54
Type 1/Type 12
2324
2324
1569
1962
1130
1130
2204
2204
1400
1800
606
606
1004
1246
F1/F3
F3 F1
21/54
Type 1/Type 12
500–710 kW at 400 V
(380–480 V)
710–900 kW at 690 V
(525–690 V)
F3
F4
500–710 kW at
800–1000 kW at
400 V
400 V
(380–480 V)
(380–480 V)
710–900 kW at
1000–1400 kW at
690 V
690 V
(525–690 V)
(525–690 V)
21, 54
21, 54
Type 1/Type 12
Type 1/Type 12
2324
2324
2159
2559
1130
1130
2204
2204
2000
2400
606
606
1299
1541
F2/F4
F4 F2
21/54
Type 1/Type 12
800–1000 kW at 400 V
(380–480 V)
1000–1400 kW at 690 V
(525–690 V)
3
3
15

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the VLT HVAC Drive FC 102 and is the answer not in the manual?

Table of Contents

Save PDF