6.2.5
ECO Mode Start-up Procedures
WARNING:
Before turning on the UPS, please read 6.1 Pre Start-up & Pre Turn-off Warnings
thoroughly and ensure that the precautions and instructions have been followed.
Step 1
Ensure that the external maintenance bypass cabinet's Manual Bypass Breaker or Switch
(Q3) is in the OFF position.
Step 2
Switch ON every external battery cabinet's breaker (Q5).
Step 3
Switch ON the external maintenance bypass cabinet's Output Breaker or Switch (Q4).
Step 4
Switch ON the external maintenance bypass cabinet's Bypass Breaker or Switch (Q2), wait
for the LCD initial screen, and switch ON the external maintenance bypass cabinet's Input
Breaker or Switch (Q1).
If the bypass input is within the normal range, the UPS will run in Bypass mode.
Step 5
Log in as Administrator. For the Administrator password, please contact service
personnel.
97