7.1

Single Unit Operation Procedures

7.1.1 Normal Mode Start-up Procedures (Single)

Before start-up, ensure that each breaker (including every external battery cabinet's
1
breaker) is in the OFF position.
Turn on each external battery cabinet's breaker.
2
Turn on the output breaker.
3
For single input, please turn on the input breaker. For dual input, please turn on the input
4
breaker and bypass breaker.
5
Press the ON key (
6
After the NORMAL LED indicator (
7
mode start-up procedures are completed.

7.1.2 Battery Mode Start-up Procedures (Single)

Turn on each external battery cabinet's breaker.
1
Turn on the output breaker.
2
Press the ON key (
3
Press the ON key (
4
After the BATTERY LED indicator (
5
mode start-up procedures are completed.

7.1.3 Bypass Mode Start-up Procedures (Single)

Before start-up, ensure that each breaker (including every external battery cabinet's
1
breaker) is in the OFF position.
Turn on each external battery cabinet's breaker.
2
Turn on the output breaker.
3
For single input, please turn on the input breaker. For dual input, please turn on the input
4
breaker and bypass breaker.
After the BAPASS LED indicator (
5
mode start-up procedures are completed.
) once to turn on the LCD display.
53
Chapter 7
) illuminates, it means that the normal
) illuminates, it means that the battery
) illuminates, it means that the bypass
UPS Operation