Eco Mode Start-Up Procedures - Delta Modulon DPH Series User Manual

Hide thumbs Also See for Modulon DPH Series:
Table of Contents

Advertisement

6.2.5 ECO Mode Start-up Procedures

1
Ensure that the Manual Bypass Breaker (Q3) is in the OFF position.
2
Switch ON every external battery cabinet's breaker (Q5).
3
Switch ON the Input Breaker (Q1), Bypass Breaker (Q2) and Output Breaker (Q4).
4
After you switch on the Input Breaker (Q1) and Bypass Breaker (Q2), each auxiliary
power card's LED indicator will illuminate green and the following status will occur
simultaneously.
(1) The system and each power module will start initialization. After each power
For the locations of the parallel communication card, auxiliary power cards, power
modules and associated LED indicators, please refer to Figure 6-1.
Modulon DPH Series
WARNING:
1. For parallel units, please follow 6.2.3 Bypass Mode Start-up Procedures
to turn on each parallel UPS. After confirming that parallel operation works
normally, follow the procedures below step by step.
2. For parallel units, ensure that every operation procedure mentioned below is
synchronized to all parallel UPSs.
parallel ones, please contact service personnel.
power module will start establishing DC BUS voltage and each power module's
LED indicator will illuminate green.
the card will start initialization. After initialization, the parallel communication
card's LED indicator will illuminate green.
NOTE:
If you purchase an additional parallel communication card (optional) and
install it in the parallel communication card slot shown in Figure 4-12,
initialization. After initialization, the parallel communication card's LED
indicator will illuminate yellow. For more information, please refer to 4.1.7
Parallel Communication Card.
6-18

Advertisement

Table of Contents
loading

Table of Contents