Specifications
8 Specifications
8.1 Mains Supply 3x380–480 V AC
Frequency converter typical shaft
output [kW]
Enclosure protection rating IP20
Output current
Shaft output [kW]
Continuous (3x380–440 V) [A]
Continuous (3x441–480 V) [A]
Intermittent (60 s overload) [A]
Continuous kVA (400 V AC) [kVA]
Continuous kVA (480 V AC) [kVA]
Maximum input current
Continuous (3x380–440 V) [A]
Continuous (3x441–480 V) [A]
Intermittent (60 s overload) [A]
8
8
Additional specifications
Maximum cable cross-section (mains,
motor, brake, and load sharing)
[mm
2
(AWG)]
Estimated power loss at rated
maximum load [W]
Weight [kg], enclosure protection
rating IP20
3)
Efficiency [%]
Table 8.1 Mains Supply 3x380–480 V AC - Heavy Duty
48
VLT
HK37
HK55
0.37
0.55
J1
0.37
0.55
1.2
1.1
1.9
0.84
1.18
0.9
1.2
1.0
1.9
20.88
25.16
2)
2.3
96.2
97.0
Danfoss A/S © 04/2015 All rights reserved.
®
AutomationDrive FC 360
HK75
H1K1
H1K5
0.75
1.1
1.5
J1
J1
J1
J1
0.75
1.1
1.5
1.7
2.2
3
3.7
1.6
2.1
2.8
3.4
2.7
3.5
4.8
5.9
1.53
2.08
2.57
1.3
1.7
2.5
2.8
1.6
2.1
2.6
3.5
1.2
1.8
2.0
2.9
2.6
3.4
4.2
5.6
30.01
40.01
52.91
2.3
2.3
2.3
2.3
97.2
97.4
97.4
1)
H2K2
H3K0
H4K0
2.2
3
4
J1
J2
J2
2.2
3
4
5.3
7.2
9
4.8
6.3
8.2
8.5
11.5
14.4
3.68
4.99
6.24
4.0
5.2
6.8
4.7
6.3
8.3
3.9
4.3
6.8
7.5
10.1
13.3
4(12)
73.97
94.81
115.5
2.5
3.6
3.6
97.6
97.5
97.6
H5K5
H7K5
5.5
7.5
J2
J3
5.5
7.5
12
15.5
11
14
19.2
24.8
8.32
10.74
9.1
11.6
11.2
15.1
9.4
12.6
17.9
24.2
157.54
192.83
3.6
4.1
97.7
98.0
MG06A602
Need help?
Do you have a question about the VLT AutomationDrive FC 360 and is the answer not in the manual?