Danfoss VLT AutomationDrive FC 360 Quick Manual page 55

Hide thumbs Also See for VLT AutomationDrive FC 360:
Table of Contents

Advertisement

Specifications
Analog outputs
Number of programmable analog outputs
Terminal number
Current range at analog output
Maximum resistor load to common at analog output
Accuracy on analog output
Resolution on analog output
The analog output is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
Control card, RS485 serial communication
Terminal number
Terminal number 61
The RS485 serial communication circuit is galvanically isolated from the supply voltage (PELV).
Digital outputs
Programmable digital/pulse outputs
Terminal number
Voltage level at digital/frequency output
Maximum output current (sink or source)
Maximum load at frequency output
Maximum capacitive load at frequency output
Minimum output frequency at frequency output
Maximum output frequency at frequency output
Accuracy of frequency output
Resolution of frequency output
1) Terminal 27 and 29 can also be programmed as input.
The digital output is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
Control card, 24 V DC output
Terminal number
Maximum load
The 24 V DC supply is galvanically isolated from the supply voltage (PELV), but has the same potential as the analog and digital
inputs and outputs.
Relay outputs
Programmable relay outputs
Relay 01
Maximum terminal load (AC-1)
Maximum terminal load (AC-15)
Maximum terminal load (DC-1)
Maximum terminal load (DC-13)
Maximum terminal load (AC-1)
Maximum terminal load (AC-15)
Maximum terminal load (DC-1)
Minimum terminal load on 01–03 (NC), 01–02 (NO)
1) IEC 60947 t 4 and 5
The relay contacts are galvanically isolated from the rest of the circuit by reinforced isolation.
Control card, +10 V DC output
Terminal number
Output voltage
Maximum load
The 10 V DC supply is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
MG06A602
Quick Guide
1)
on 01–02/04–05 (NO) (Resistive load)
1)
on 01–02/04–05 (NO) (Inductive load @ cosφ 0.4)
1)
on 01–02/04–05 (NO) (Resistive load)
1)
on 01–02/04–05 (NO) (Inductive load)
1)
on 01–03/04–06 (NC) (Resistive load)
1)
on 01–03/04–06 (NC) (Inductive load @ cosφ 0.4)
1)
on 01–03/04–06 (NC) (Resistive load)
Danfoss A/S © 04/2015 All rights reserved.
Maximum error: 0.8% of full scale
68 (P,TX+, RX+), 69 (N,TX-, RX-)
Common for terminals 68 and 69
Maximum error: 0.1% of full scale
01–03 (NC), 01–02 (NO), 04–06 (NC), 04–05 (NO)
24 V DC 10 mA, 24 V AC 20 mA
2
45, 42
0/4–20 mA
500 Ω
10 bit
2
1)
27, 29
0–24 V
40 mA
1 kΩ
8
8
10 nF
4 Hz
32 kHz
10 bit
12
100 mA
2
250 V AC, 3 A
250 V AC, 0.2 A
30 V DC, 2 A
24 V DC, 0.1 A
250 V AC, 3 A
250 V AC, 0.2 A
30 V DC, 2 A
50
10.5 V ±0.5 V
15 mA
53