Specifications; Power-Dependent Specifications - Danfoss VLT FC 100 Instruction Manual

110–400 kw d-frame hvac drive
Hide thumbs Also See for VLT FC 100:
Table of Contents

Advertisement

Specifications

10 Specifications

10.1 Power-dependent Specifications

Normal Load*
Typical Shaft output at 400 V [kW]
Typical Shaft output at 460 V [hp]
Typical Shaft ouptut at 480 V [kW]
Enclosure IP21
Enclosure IP54
Enclosure IP20
Output current
Continuous (at 400 V) [A]
Intermittent (60 s overload) (at 400
V) [A]
Continuous (at 460/500 V) [A]
Intermittent (60 s overload) (at
460/500 V) [kVA]
Continuous kVA (at 400 V) [kVA]
Continuous kVA (at 460 V) [kVA]
Max. Input current
Continuous (at 400 V) [A]
Continuous (at 460/500 V) [A]
Max. cable size: line power, motor,
brake and load share mm (AWG)]
Max. external electrical fuses [A]
Estimated power loss at 400 V [hp,
W]
Estimated power loss at 460 V [hp,
W]
Weight, enclosure IP21, IP54 kg
(lbs)
Weight, enclosure IP20 kg (lbs)
Efficiency
Output frequency
*Normal overload=110% current for 60 s
Table 10.1 Line Power Supply 3x380–480 V AC
®
VLT
HVAC Drive D-Frame
Instruction Manual
N110
N132
NO
NO
110
132
150
200
132
160
D1h
D1h
D1h
D1h
D3h
D3h
212
260
233
286
190
240
209
264
147
180
151
191
204
251
183
231
2x95 (2x3/0)
315
350
3.426, 2555
3.955, 2949
3.027, 2257
3.646, 2719
62 (135)
62 (135)
®
MG16D222 - VLT
is a registered Danfoss trademark
N160
N200
NO
NO
160
200
250
300
200
250
D1h
D2h
D1h
D2h
D3h
D4h
315
395
347
435
302
361
332
397
218
274
241
288
304
381
291
348
400
550
5.048, 3764
5.510, 4109
4.857, 3622
4.775, 3561
0.98
0–590 Hz
N250
N315
NO
NO
250
315
350
450
315
355
D2h
D2h
D2h
D2h
D4h
D4h
480
588
528
647
443
535
487
588
333
407
353
426
381
463
463
567
348
427
427
516
2x185 (2x350)
630
800
6.878, 5129
8.935, 6663
6.112, 4558
7.648, 5703
125 (275)
125 (275)
10-1
10
10

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the VLT FC 100 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Table of Contents