Operating Guide | VLT® Refrigeration Drive FC 103
9 Specifications
9.1 Electrical Data
9.1.1 Electrical Data, 380–480 V AC
Table 42: Electrical Data, Mains Supply 3x380–480 V AC
FC 103
High/normal overload
High overload=150% or 160% torque for a duration of 60 s.
Normal overload=110% torque for a duration of 60 s.
Typical shaft output at 400 V [kW]
Typical shaft output at 460 V [hp]
Typical shaft output at 500 V [kW]
Enclosure size
Output current (3-phase)
Continuous (at 400 V) [A]
Intermittent (60 s overload) (at 400 V) [A]
Continuous (at 460/480 V) [A]
Intermittent (60 s overload) (at 460/480 V) [A]
Continuous kVA (at 400 V) [kVA]
Continuous kVA (at 460 V) [kVA]
Continuous kVA (at 480 V) [kVA]
Maximum input current
Continuous (at 400 V) [A]
Continuous (at 460/480 V) [A]
Maximum number and size of cables per phase (E1h)
- Mains and motor without brake [mm
- Mains and motor with brake [mm
2
- Brake or regen [mm
(AWG)]
Maximum number and size of cables per phase (E3h)
2
- Mains and motor [mm
(AWG)]
2
- Brake [mm
(AWG)]
- Load share or regen [mm
Maximum external mains fuses [A]
Estimated power loss at 400 V [W]
Estimated power loss at 460 V [W]
Danfoss A/S © 2020.01
2
(AWG)]
2
(AWG)]
2
(AWG)]
(1)
(2) (3)
(2) (3)
N355
NO
355
500
400
E1h/E3h
658
724
590
649
456
470
491
634
569
5x240 (5x500 mcm)
5x240 (5x500 mcm)
4x240 (4x500 mcm)
4x240 (4x500 mcm)
2x185 (2x350 mcm)
2x185 (2x350 mcm)
6x240 (6x500 mcm)
6x240 (6x500 mcm)
2x185 (2x350 mcm)
2x185 (2x350 mcm)
4x185 (4x350 mcm)
4x185 (4x350 mcm)
800
6928
5910
AQ275652766279en-000101 / 130R0707| 127
Specifications
N400
N450
NO
NO
400
450
550
600
500
530
E1h/E3h
E1h/E3h
745
800
820
880
678
730
746
803
516
554
540
582
564
607
718
771
653
704
5x240 (5x500 mcm)
4x240 (4x500 mcm)
2x185 (2x350 mcm)
6x240 (6x500 mcm)
2x185 (2x350 mcm)
4x185 (4x350 mcm)
800
800
8036
8783
6933
7969