8 Specifications

8.1 Electrical data

8.1.1 Mains Supply 1x200–240 V AC
Table 25: Mains Supply 1x200–240 V AC, Normal Overload 110% for 1 Minute, P1K1–P22K
Type designation
Typical shaft output [kW]
Typical shaft output at 240 V
[hp]
Protection rating IP20/Chassis
Protection rating IP21/Type 1
Protection rating IP55/Type
12
Protection rating IP66/NEMA
4X
Output current
Continuous (3x200–240 V) [A]
Intermittent (3x200–240 V)
[A]
Continuous kVA at 208 V [kVA]
Maximum input current
Continuous (1x200–240 V) [A]
Intermittent (1x200–240 V)
[A]
Maximum pre-fuses [A]
Additional specifications
Maximum cable cross-section
2
(mains, motor, brake) [mm
(AWG)]
Maximum cable cross-section
for mains with disconnect
2
switch [mm
(AWG)]
Maximum cable cross-section
for mains without disconnect
2
switch [mm
(AWG)]
Cable insulation temperature
rating [°C (°F)]
Estimated power loss
at rat-
(3)
ed maximum load [W]
(4)
Danfoss A/S © 2020.09
P1K1
P1K5
P2K2
1.1
1.5
2.2
1.5
2.0
3.0
A3
B1
B1
A5
B1
B1
A5
B1
B1
6.6
7.5
10.6
7.3
8.3
11.7
2.4
2.7
3.8
12.5
15
20.5
13.8
16.5
22.6
20
30
40
0.2–4 (4–10)
16 (6)
16 (6)
16 (6)
16 (6)
16 (6)
16 (6)
75 (167)
75 (167)
75 (167)
44
30
44
P3K0
P3K7
P5K5
3.0
3.7
5.5
4.0
5.0
7.5
B1
B1
B1
B1
B1
B1
B1
B1
B1
12.5
16.7
24.2
13.8
18.4
26.6
4.5
6.0
8.7
24
32
46
26.4
35.2
50.6
40
60
80
10 (7)
16 (6)
16 (6)
16 (6)
16 (6)
16 (6)
16 (6)
75 (167)
75 (167)
75 (167)
60
74
110
AJ300847815559en-000101 / 130R0337 | 71
Specifications
P7K5
P15K
P22K
7.5
15
22
10
20
30
B2
C1
C2
B2
C1
C2
B2
C1
C2
30.8
59.4
88
33.4
65.3
96.8
11.1
21.4
31.7
59
111
172
64.9
122.1
189.2
100
150
200
35 (2)
50 (1/0)
95 (4/0)
25 (3)
50 (1/0)
2 x 50 (2 x
1/0)
(1)(2)
25 (3)
50 (1/0)
95 (4/0)
75 (167)
75 (167)
75 (167)
150
300
400