Specifications
Frequency converter typical
shaft output [kW]
Enclosure protection rating
IP20
Output current
Continuous (3x380–440 V) [A]
Continuous (3x441–480 V) [A]
Intermittent (60 s overload) [A]
Continuous kVA (400 V AC)
[kVA]
Continuous kVA (480 V AC)
[kVA]
Maximum input current
Continuous (3x380–440 V) [A]
Continuous (3x441–480 V) [A]
Intermittent (60 s overload) [A]
Additional specifications
Maximum cable size (mains,
motor, brake) [mm
2
(AWG)]
Estimated power loss at rated
2)
maximum load [W]
Weight [kg], enclosure
protection rating IP20
Efficiency [%]
3)
Table 8.2 Mains Supply 3x380–480 V AC - Heavy Duty
MG06A602
Quick Guide
H11K
H15K
H18K
11
15
18.5
J4
J4
J5
23
31
37
21
27
34
34.5
46.5
55.5
15.94
21.48
25.64
17.5
22.4
28.3
22.1
29.9
35.2
18.4
24.7
29.3
33.2
44.9
52.8
16(6)
289.53
393.36
402.83
9.4
9.5
12.3
97.8
97.8
98.1
1)
Danfoss A/S © 04/2015 All rights reserved.
H22K
H30K
H37K
22
30
37
J5
J6
J6
42.5
61
73
40
52
65
63.8
91.5
109.5
29.45
42.3
50.6
33.3
43.2
54.0
41.5
57
70.3
34.6
49.3
60.8
62.3
85.5
105.5
50(1/0)
467.52
630
848
12.5
22.4
22.5
97.9
98.1
98.0
H45K
H55K
H75K
45
55
75
J6
J7
J7
90
106
147
77
96
124
135
159
220.5
62.4
73.4
101.8
64.0
79.8
103.1
84.2
102.9
140.3
72.7
88.8
121.1
126.3
154.4
210.5
85(3/0)
1175
1250
1507
22.6
37.3
38.7
97.7
98.0
98.2
49
8
8
Need help?