FTP Server Settings

Set the file transfer function (FTP server).
Item
FTP Server
Login Name
Advanced

Password Setting

Settings

FTP Timer Settings

Allow Online Change
Password Setting

■Current Password

Enter the current password for login to the Ethernet-equipped module.
Default password (initial setting) is the following.
Module
RJ71EN71, RnENCPU (network part)
CPU module (built-in Ethernet port part)
Although the default password can be used, it is recommended to change it to another password to prevent unauthorized
access.
■New Password, Confirm New Password
Enter the new password in "New Password" and "Confirm New Password" when changing the password.
Set a password within 0 to 32 one-byte characters. Number, alphabet, special character (?,!&\%#*) can be used.
FTP Timer Settings
■Command Input Monitoring Timer
Set the monitoring time for the Ethernet-equipped module to monitor the command input time from the FTP client
It is recommended to use the default value (900s) for this timer value as much as possible.
When changing the setting value, determine the command input monitoring timer value upon consulting with the administrator
of the external device or system.
Set a value within the following range.
Unit
s
*1
ms
*1 Set in increments of 100ms.
The FTP connection is disconnected if there is no command input from the FTP client side within the time of the command
input monitoring timer value after the FTP client login.
When restarting the file transfer, start over from the login operation again.
2 PARAMETER SETTINGS
252
2.3 Application Settings
Description
Select whether to use the file transfer function (FTP server) of the
Ethernet-equipped module.
Set the login name to be used for file transfer request (login) from the
external device.
Set the password to be used for file transfer request (login) from the
external device. ( Page 252 Password Setting)
Set the following timers used for the file transfer function (FTP server).
( Page 252 FTP Timer Settings)
• Command Input Monitoring Timer
• Response Monitoring Timer
Select whether to enable data writing from the external device using
the file transfer function (FTP server) while the CPU module is in RUN
state.
Password
RJ71EN71
RCPU
Setting range
1 to 16383
100 to 16383000
Setting range
• Not Use
• Use
(Default: Not Use)
12 characters maximum (one-byte
alphanumeric character)
[Default]
• RJ71EN71 and RnENCPU (network
part): RJ71EN71
• CPU module (built-in Ethernet port
part): RCPU
• Disable
• Enable
(Default: Disable)