Modbus/Tcp Settings; Cpu Response Monitoring Timer - Mitsubishi Electric MELSEC iQ-RJ71EN71 User Manual

Ethernet
Hide thumbs Also See for MELSEC iQ-RJ71EN71:
Table of Contents

Advertisement

MODBUS/TCP Settings

Set MODBUS/TCP.
Item
To Use or Not to Use MODBUS/TCP
Setting

CPU Response Monitoring Timer

Device Assignment
CPU Response Monitoring Timer
Set the time for monitoring the response from the CPU module.
When the CPU module does not send a response within the set time after the reception of a request message from the
MODBUS/TCP master device, the state of waiting for the response from the Ethernet-equipped module is canceled.
Set the CPU Response Monitoring Timer within the following range.
Unit
s
ms
2 PARAMETER SETTINGS
254
2.3 Application Settings
Description
"Use" is displayed when a MODBUS/TCP connection device is added
in "External Device Configuration" under "Basic Settings". ("To Use or
Not to Use MODBUS/TCP Setting" cannot be edited.)
Set the time for monitoring the response from the CPU module.
(Page 254 CPU Response Monitoring Timer)
Set the parameters to associate the MODBUS devices with the device
memory areas of the CPU module.
(Page 255 Device Assignment)
Setting range
1 to 16383
100 to 16383000 (in increments of 100ms)
Setting range
• Not Use
• Use
(Default: Not Use)