The Access Cannot Be Allowed/Denied Correctly By The Ip Filter; Remote Password Does Not Work - Mitsubishi Electric MELSEC iQ-RJ71EN71 User Manual

Ethernet
Hide thumbs Also See for MELSEC iQ-RJ71EN71:
Table of Contents

Advertisement

Access using the file transfer function (FTP client) cannot be performed.
When the CPU module cannot access to the external device (FTP server) during execution of the file transfer function (FTP
client), check the following items and take action.
Check item
Is a value other than 0000H stored in (s1)+1 (Completion status) of the
SP.FTPPUT or SP.FTPGET instruction?
The time setting function (SNTP client) cannot be performed normally.
When the time setting function (SNTP client) cannot be performed normally, check the following items and take action.
Check item
Is the time setting function (SNTP client) is enabled for the Ethernet-equipped
module?
Is "SNTP Server IP Address" set correctly?
If the above action does not solve the problem, perform the module communication test to check for hardware failure. (
Page 284 Module communication test)
*1 The module communication test cannot be performed for the CPU module (built-in Ethernet port part). Perform the troubleshooting of
the CPU module and check for hardware failure. ( MELSEC iQ-R CPU Module User's Manual (Startup))

The access cannot be allowed/denied correctly by the IP filter.

When the access cannot be allowed/denied correctly by the IP filter, check the following items and take action.
Check item
Is "Access from IP address below" correctly set in "IP Filter Settings" under
"Security" of "Application Settings"?
Are the IP addresses set in "IP Address" in "IP Filter Settings" under "Security"
of "Application Settings"?
Is the IP address of the proxy server set to be allowed?

Remote password does not work.

When the remote password does not work, check the following items and take action.
Check item
Is the remote password setting of the target connection disabled in the
"Remote Password Detail Setting" window?
3 TROUBLESHOOTING
304
3.4 Troubleshooting by Symptom
Action
Take action for the error code stored in (s1)+1 (Completion status), and
execute the instruction again. ( Page 310 List of Error Codes)
Action
Set "Time Setting (SNTP Client)" under "Time Setting" of "Application
Settings" to "Use". ( Page 259 Time Setting)
Change the "SNTP Server IP Address" under "Time Setting" in "Application
Settings" to the correct IP address. ( Page 259 Time Setting)
*1
Action
Correct the setting of "Access from IP address below".
Correct the IP addresses.
When the IP addresses are specified by range, check also "IP Address
Excluded from Range".
Set the IP address of the proxy server to be denied.
Action
If the remote password is disabled, change the setting so that it is enabled.
( Page 174 Remote password)

Hide quick links: