Standard Signal Output 1 - ProMinent DULCOMETER D1C Operating Instructions Manual

Table of Contents

Advertisement

Complete Operating Menu / Description
Feed forward control
Only with feed forward control
feed forward ctrl.:
setting ?
Feed forward control (Flow) as per identity code
Feed forward control
rated value
Feed forward control
effect
Max. add. regulated value

Standard signal output 1

Access to all setting menus can be blocked with an access code !
Only with standard signal output
mA output 1
setting ?
feed forward ctrl.:
feed forward ctrl.:
Hz / mA
rated value
10 Hz
10.00 Hz
Possible values
Initial value
Increment
None
10 Hz
500 Hz
Standard signal
0...20 mA
4...20 mA
4...20 mA
10 Hz
0.01 Hz
500 Hz
1 Hz
20 mA
0.1 mA
multiplicative
multiplicative
additive
100 %
1 %
mA output 1
measured value
0...20 mA
feed forward ctrl.:
disturb. variable
additive
Lower value Upper value
0.1 Hz
10 Hz
5 Hz
500 Hz
0/4 mA
20 mA
-500 %
+500 %
control
control output
positive chlor
negative dechlor
Control with standard signal
mA output 1
measured value
0.00 ppm
0 mA =
20 mA =
2.00 ppm
Only with correction value
mA output 1
correcting value
5.00 pH
0 mA =
20 mA =
9.50 pH
feed forward ctrl.:
max. additive
regulated value:
100%
D1C2-Cl-029-GB
Remarks
Signal processing:
Signal <0,02 Hz = No flow
Signal <0,2 Hz = No flow
Signal <0,2 mA = No flow
Signal <4,2 mA = No flow
Dependent on signal type.
Maximum limitation
of range used.
only with additive feed forward control
mA output 1
control output
0%
0 mA =
20 mA =
100%
D1C2-Cl-027-GB