5. Diagnostics and error handling

5.3.1 Behaviour in response to original module faults

Chan­
FP-LED
nel er­
ror LED
Tab. 5/7:
Behaviour in response to module faults
5-10
Module
Er­
Error description
error
ror
LED
no.
5
Undervoltage in the power
supply
61
Overvoltage of the supply
voltage
65
Set PROFIsafe address does
not correlate with safety
parameterization
(F_Dest_Add)
66
Error in safe communication
67
The chronological sequence
for PROFIsafe communica­
tion is impaired
69
Fault in safe parameteriza­
tion (safety parameteriza­
tion invalid)
75
Overtemperature of the in­
put module
Short circuit/overload in a
cycle output
145
Input module has detected
a fault during a self-test
All input channels on the input module are passivized in re­
sponse to module faults
After remedial action: Reintegrate the input module.
Remedy
Correct power supply
voltage or remedy the
short circuit
Correct power supply
voltage
Check and correct set
address / parameter
è Chapter 2.4 and 3.8
Transmit new parameters
Rectify source of fault
Check communication
paths
Check timeout time
è Chapter 3.8
Check parameters in the
PROFIsafe protocol
Transmit new parameters
Remedy overtemperature
Remedy short circuit/
overload on T0, T2, T4, T6
Switch CPX terminal back
on again
Replace the input module
Festo P.BE-CPX-F8DE-P-E N en 1610a English