3. Commissioning
PROFIsafe
General description
parameters
F_Par_Version
Specifies the PROFIsafe operat­
ing mode of the device.
The setting 1 corresponds to
PROFIsafe V2-MODE.
F_Source_Add
Unique PROFIsafe source ad­
(PROFIsafe
dress of the F-Host.
source address)
F_Dest_Add
Unique PROFIsafe target ad­
(PROFIsafe target
dress of the F-Device within the
address)
PROFIsafe network.
The target address set by the
configuration software must
match the PROFIsafe address
set on the input module using
the DIL switch.
F_WD_Time
Time period (Watchdog Time)
within which a valid current
safety telegram must arrive
from the F-Host. Otherwise, the
F-Device goes into the safe
status.
F_iPar_CRC
CRC through the individual
device parameters
(i-parameter).
Tab. 3/3:
PROFIsafe parameters
3-8
For CPX-F8DE-P, the fol­
lowing apply:
– CPX-F8DE-P works
exclusively in PROFIsafe
V2-MODE.
– Unique PROFIsafe source
address of the F-Host.
– CPX-F8DE-P compares
both settings to check the
authenticity of the con­
nection è Chapter 2.4.
– The time period must be
short enough that the sys­
tem can react quickly
enough to communication
failures or malfunctions.
On the other hand, the
time period must be long
enough to tolerate typical
delays in transmission.
The clock time for calling
the safety program must
be less than the time peri­
od set here.
– CPX-F8DE-P makes no indi­
vidual device parameters
available.
Festo P.BE-CPX-F8DE-P-E N en 1610a English
Value
– 1
(not
changeable)
Specified
through
F-Host
– 1 ... 1022
(0 and 1023
are not per­
mitted)
– 50 ... 65535
[ms]
– 0
(not
changeable)