1. System overview CPX-F8DE-P
Connection block
CPX-AB-8-KL-4POL
CPX-AB-ID-P
Tab. 1/1:
Permitted connection blocks
Festo P.BE-CPX-F8DE-P-E N en 1610a English
Description
Terminal strip connection technology
– 2 terminal strips, 16-pin (4 x 4-pin)
– all cores can be placed individually in a spring tension clamp
– Connections are arranged in groups of 4, one functional-earth
connection per group
– for the use of sensors with static or switched 24V power supply
– for the use of sensors with mechanical switch contacts and
electronic sensors with a current consumption up to 0.7A
– Degree of protection IP20
– Degree of protection IP65 with use of cover AK-8KL
Connection block without connection technology
– coded identifier
Information about electrical connection and display elements
è Chapter 2.2.