Festo CPX-F8DE-P Manual page 56

Input module terminal cpx
Hide thumbs Also See for CPX-F8DE-P:
Table of Contents

Advertisement

1. System overview CPX-F8DE-P
1-24
Function mode 2 – 1oo1 Test
(T0, T2, T4, T6 static off )
Signal evaluation of up to 2 independent single-channel
switches/sensors (NO or NC) per channel pair. In this function
mode, T0, T2, T4, T6 are not connected to any voltage.
Circuit diagram
Tab. 1/15: Function mode 2 – 1oo1 Test
Function mode 2 can be used as a test modewhen you con­
nect sensors for function mode 1
This way, a safety controller used alternately in function
modes 1 and 2 can generate user-specific test signals and
evaluate if a zero crossing has taken place.
Software-generated test signals only work with the following
connection blocks:
CPX-M-AB-4-M12X2-5POL-T
CPX-AB-8-KL-4POL.
Note
During the test period, safety requirements cannot be eval­
uated with the safety controller.
Function mode 2 can alternatively be used for resetting
sensors with self-monitoring electronic outputs.
Channel pair ports
T0
T2
T4
E1
E3
E5
0 V
E0
E2
E4
T1/FE
T3/FE
T5/FE
Festo P.BE-CPX-F8DE-P-E N en 1610a English
T6
E7
E6
T7/FE