1. System overview CPX-F8DE-P
1.3
Functional method of the input module
Festo P.BE-CPX-F8DE-P-E N en 1610a English
Automatic acknowledgment is possible by holding the ac
knowledgment bit permanently at "1".
If acknowledged while an error is still present, the input im
age remains in safe mode. In the event of undesired automat
ic acknowledgment, a safety program must ensure that the
safety controller cancels that acknowledgment.
Note
In the event of a restart of the F-Host (Stop è Run), the
channel monitoring function of the input module
CPX-F8DE-P also restarts.
If the cause of the error is still present, the channel error
will be triggered again.
The inputs on the input module are always evaluated using 2
independent internal channel paths. To this end, the input
module is equipped with 2 processors that monitor one an
other continuously and can also monitor the input channels
for cross-circuiting, depending on the selected function
modes.
The input module is designed such that the input channels
can provide either secure data or no data at all, even when a
fault is present in the system, e.g. with:
–
overvoltage, undervoltage, overload, short circuit and
cross circuit
–
Failure or malfunction of communication via PROFIsafe
–
Failure or defect of individual safety-determining compon
ents of the input module.